Siemens SIMATIC NET CP 142-2 Manual page 48

Table of Contents

Advertisement

B8976111/02
4.2.1.7 Get_Permanent_Configuration
Meaning
This call returns the desired configuration data of an addressed slave stored permanently in the
EEPROM (I/O configuration data and the ID codes).
Structure of the job data in the send buffer
Bit 7
Byte 0
0 H
Byte 1
Structure of the job data in the receive buffer
Bit 7
Byte 0
ID code
4.2.1.8 Store_Actual_Parameters
Meaning
This call stores the actual I/O configuration data and actual ID codes of all slaves on the AS-Interface
permanently on the EEPROM as desired configuration data. The list of activated slaves (LAS) is also
entered in the list of configured slave (LPS).
When executing this command, the CP changes to the offline phase and then switches


to the normal mode (cold restart on the CP).

The call is not executed in the protected mode.

Structure of the job data in the send buffer
Bit 7
Byte 0
0 H
Bit 0
6 H
Slave address
Bit 0
I/O configuration
Bit 0
7 H
4-11
AS-i Master Module CP 142-2

Advertisement

Table of Contents
loading