Electrical Safety; Specifications - Thermoscreens T Series Operation And Maintenance

Recessed range
Table of Contents

Advertisement

2.

ELECTRICAL SAFETY

Electrical Supply and Wiring to the Air Curtain
All electrical wiring and connections MUST be carried out by a competent qualified electrician in
accordance with the latest edition of the IEE wiring regulations and/or local statutory regulations.
A 1 phase or 3 phase local isolator having a contact separation of at least 3mm on all
poles must be fitted in the electrical supply to the air curtain and located in an accessible
position adjacent to the unit.
The appliance must be connected by cables having an appropriate heat resistant
temperature rating.
All supply cables, circuit breakers and other electrical installation equipment must be
correctly sized for the air curtain model being installed; see section 3: Specifications.
Models operating on 3 phase electrical supply - see section 3: Specifications - require a
neutral connection (3N~).
A 25mm size cable gland or conduit connector of IP21 rating or above should be used for
the Electrical Supply into the air curtain.
See Wiring Diagram for connecting electrical supply and control cables to the air curtain.
The air curtain must be earthed.
3.

SPECIFICATIONS

Air Curtain
Model No
T1000AR
T1500AR
T2000AR
T1000WR
T1500WR
T2000WR
T1000E9R
T1000E12R
T1500E12R
T1500E18R
T2000E18R
T2000E24R
T9901012-1-1 UK (v9)
Rated
Electrical
Electrical
Supply
Power Input
(V/ph/Hz)
(kW)
230/1/50
0.25
230/1/50
0.35
230/1/50
0.45
230/1/50
0.25
230/1/50
0.35
230/1/50
0.45
400/3/50
9.25
400/3/50
12.25
400/3/50
12.35
400/3/50
18.35
400/3/50
18.45
400/3/50
24.45
Rated
Heat Output
Current
[Low/High]
per phase
(kW)
(A)
1.1
N/A
1.7
N/A
2.0
N/A
1.1
6.0 / 12.0
1.7
9.0 / 18.0
2.0
12.0 / 24.0
14.1
6.0 / 9.0
18.7
6.0 / 12.0
18.9
6.0 / 12.0
27.9
9.0 / 18.0
28.1
12.0 / 18.0
36.8
12.0 / 24.0
Table 1
Weight
(kg)
27
40
50
29
42
53
28
28
41
41
52
52
Page | 3