Aqua Tempo Super II
4.19 PU/FF Troubleshooting
4.19.1
Digital display output
4.19.2
Description
1PU indicates fan module A protection.
2PU indicates fan module B protection.
FF indicates PU protection has displayed 2times. When a FF occurred 3 times in 20 minutes, a manual system restart
is required before the system can resume operation.
All units stop running. The cause of an HH error should be addressed promptly in order to avoid system damage.
Error code is only displayed on the main PCB and user interface.
4.19.3
Possible causes
Switch SW1 incorrectly set.
Power or communication wires not connected properly.
Fan motor blocked or has failed.
Power supply abnormal.
AC filter board damaged.
Fan module damaged.
Inverter module PCB damaged.
88