Midea Aqua Tempo Super II Series Service Manual page 59

Commercial air conditioners
Hide thumbs Also See for Aqua Tempo Super II Series:
Table of Contents

Advertisement

Aqua Tempo Super II
4.6 E9 Troubleshooting
4.6.1
Digital display output
4.6.2
Description
 Water flow failure.
 E9 indicates a water flow switch error. When an E9 error occurs 3 times in 60 minutes, a manual system restart is
required before the system can resume operation.
 All units stop running.
 Error code is displayed on main PCB and user interface.
4.6.3
Possible causes
 The wire circuit is short connected or open.
 Water flow rate is too low.
 Water flow switch damaged.
 Damaged main PCB.
58