Aqua Tempo Super II
4.6 E9 Troubleshooting
4.6.1
Digital display output
4.6.2
Description
Water flow failure.
E9 indicates a water flow switch error. When an E9 error occurs 3 times in 60 minutes, a manual system restart is
required before the system can resume operation.
All units stop running.
Error code is displayed on main PCB and user interface.
4.6.3
Possible causes
The wire circuit is short connected or open.
Water flow rate is too low.
Water flow switch damaged.
Damaged main PCB.
58