Air-cooled water chillers-axial fans.
cooling capacities: from 21,18 kw to 38,7 kw.
heating capacities: from 25,2 kw to 40,3 kw.
serie mini krono 2 (22 pages)
Low profile ductable air conditioning unit (13 pages)
Summary of Contents for Hitecsa VERNE WPHBA Series
Page 1
WPHBA │ WPHA Heat pump Cooling only PACKAGED HORIZONTAL WATER-TO-AIR CONDITIONERS 091│121│141│171│201│251│351│401│501│701│751│1001│1201 Models: Cooling Capacities: from 2.4 to 41.0 kW Heating Capacities: from 2.8 to 46.4 kW IOM_WPHBA-WPHA_091a1201_207954_180610_EN...
Page 2
Thank you for trusting the Hitecsa Products. Our company has been offering the market an extended range of specialized units for air conditioning and cooling installations for over 35 years. Our approach is based on efficiency, adaptability, usability and practical solutions.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INTRODUCTION CONTENTS Purpose of this Manual This manual and any other instructive document attached as refrigeration lines design, electrical diagrams, etc. have been written to allow a correct installation, commissioning and maintenance of the unit. Therefore it is essential to read the instructions with due attention.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INTRODUCTION CONTENTS Periodic Inspections and Maintenance Carry out periodic inspections to detect possible damaged or broken pieces. If they are not repaired it could cause damage to people or stuff. Before executing any maintenance operation, cut off the unit power supply.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS SAFETY PRECAUTIONS DANGER Do not touch or adjust the safety elements inside of any unit of the system. In the repairs use only original spare parts and install them properly in the same position where old parts were placed. ...
Page 9
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS TECHNICAL SPECIFICATIONS VERNE RANGE REFRIGERANT Type R-410A Global Warming Potential (GWP) (4) 2088 Refrigerant load WPHA 0.55 Refrigerant load WPHBA COMPRESSOR Type Rotational Quantity Voltage V / ~ / Hz 230 / I / 50 EVAPORATOR FAN Type Centrifugal.
Verify the correct voltage of the nameplate and make sure it is in accordance with local power supply. In case of any flaw or anomaly detected, please contact HITECSA. RIGGING Before moving the unit, make sure that all panels are well fixed.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INSTALLATION INSTALLATION LOCATION Consult and respect the rules and local regulations which regulate the installation of air conditioning systems. Choose a site without dust and debris. Respect the appropriate service area for the equipment which will be installed. ...
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INSTALLATION DRAINAGE The indoor drain unit (of condensate water) has a 3/4” MPT connection. Condensate drain pipe diameter should be equal or larger than the unit drain connection depending on the line length and general building configuration.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INSTALLATION HYDRAULIC INSTALLATION The selection of the components and the installation shall be made by a qualified installer according to the valid local legislation and the good practice rules. Make sure that you are aware of all the local rules and regulations for hydraulic installations and that you comply with them.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INSTALLATION THE HYDRAULIC CIRCUIT AND ITS COMPONENTS The plate heat exchanger is the most fragile part of the hydraulic circuit. Therefore it is very important that the units provided with a plate exchanger work in an open hydraulic circuit and in a closed thermal circuit within the control values as stated in the following chart.
3 times the diameter of the tube. No other component or accessory shall be installed on that tube. If you use a flow switch from another supplier (not delivered by Hitecsa), refer to the instructions of the producer and respect the dimensions as previously stated.
Page 31
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INSTALLATION Installation of the paddle according to the diameter of the tube: Tube Paddle 1" - 1 ½” 2" - 2 ½” 3" - 4” 1+2+3 INSTRUCTIONS VERIFICATION OF THE PADDLE MOVEMENT ELECTRICAL CONNECTIONS ADJUSTING SCREW ADJUSTING SCREW...
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INSTALLATION WATER CONNECTIONS WITH THE OPTIONAL PRESSOSTATIC VALVE Install the by-pass solenoid valve with the optional pressostatic valve in the Heat Pump units. UNIT WATER SIDE 1. Antivibratory coupling. 2. Shut off valve 3.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS INSTALLATION ELEMENTS AND HYDRAULIC CONNECTIONS OF THE INSTALLATION DIAGRAM WPHA/BA unit Condensate drain Dry cooler Thermometer Drain Air duct Shut off valve Automatic purge Pressure gauge Expansion tank Flexible connection Water line Mesh filter Circulation pump Flow switch...
The power supply of the unit must be as indicated on the serial plate. Damage caused by the start-up of the unit in an incorrect voltage line is not covered by Hitecsa’s warranty. The unit must not be supplied with any other voltage than that indicated on the serial plate. The power supply to the unit must be within 10% of the voltage indicated on the serial plate.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS START UP It is very important to evacuate air from the system and clean dirt particles of the water circuit. The two operations must be done at the same time. At first start up the water pump for a few minutes. ...
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPERATION OPERATING LIMITS Cooling cycle INPUT TEMPERATURE MINIMUM MAXI MUM Dry indoor air 19ºC 31ºC Wet indoor air 15ºC 21ºC Water inlet 15ºC * 45ºC ** *For water inlets lower than 25ºC, it is necessary to install the presostatic valve accessory. ** On request units can be manufactured to 50 ºC.
Page 38
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPERATION INDOOR FAN TRANSMISSION ADJUSTMENT Align fan and motor pulleys: Loose fan pulley set screws. Slide fan pulley along the shaft and align with motor by using a ruler in order to ensure that is parallel to the belt. Tighten fan pulley set screws.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPERATION TH TUNE CONTROL Serial controller for standard models with µPC control board. Start / Stop Press and hold the (On / Off) button for two seconds to turn the thermostat on or off. ...
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS MAINTENANCE WARNING! Before performing any service or maintenance operation it is mandatory to turn off the main power switch of the system to avoid any personal injuries. Locked it so that nobody other than a qualified technician can switch on electrical power.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS MAINTENANCE COMPRESSOR LUBRICANT Compressors with R-410A refrigerant use POE oils. Each compressor manufacturer is using different oil for its products. The compressor or system cannot remain open to atmosphere more than 15 minutes. Compared with the mineral oil used with R22 compressors, the synthetic polyester lubricants absorb 100 times more moisture.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS MAINTENANCE REFRIGERANT CHARGE WARNING! Never use oxygen to pressurize system or purge lines for leak test. Oxygen reacts violently with oil, which can cause an explosion resulting in damage, personal injury or death. ...
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPTIONAL EC MOTOR FANS Safety instructions This document contains information to avoid personal and material damage. These instructions are not intended to be complete. If you have questions or problems, our technicians are at your disposal for any queries you wish to make. Intended use ...
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPTIONAL EC MOTOR FANS Safety instructions Explanations of symbols Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows. Attention! General hazardous area. Death or severe injury or significant property damage can occur if the corresponding precautions are not taken! Danger due to electric current Warning of dangerous voltage of dangerous current.
Page 46
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPTIONAL EC MOTOR FANS Working on device Danger due to electric current WARNING! It is generally forbidden to carry out work on electrical live parts. Protection class of the device when complete open is IP00! It is possible to touch hazardous voltages directly.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPTIONAL EC MOTOR FANS Working on device Attention, hot surface! WARNING! Temperatures of above 85ºC can occur on the motor surfaces, especially on the controller housing! Modifications / interventions in the device WARNING! For reasons of safety, no unauthorized interventions or modifications may be made on the device.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPTIONAL EC MOTOR FANS Diagnosis / Faults Trouble shooting Type of error Possible cause Remedial measures Failure line voltage. Failure of one Check line voltage. phase. Under – or overvoltage. Earth fault. Check motor connection and line voltage.
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPTIONAL EC MOTOR FANS Diagnosis / Faults Status Out with flash code Relay contact 11-14 LED Code Cause (Explanation) Fan alarms Open No line voltage Closed Normal operation without fault Closed No enable = OFF Closed Active temperature management Open...
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPTIONAL EC MOTOR FANS Rotation caused by an air flow in the wrong direction When the fan is stopped (no signal, no electrical supply, etc.), the control of the motor does not interfere if the fan rotates in wrong direction (due to, for example, an air flow).
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS OPTIONAL VENTILADORES CON MOTOR EC Cleaning Danger due to electric current ATTENTION! Voltage supply for motor must be interrupted and secured against restoration! Clean the circulation area of the air fan. Attention! ...
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS APPENDIX: SAFETY DATA R-410A Refrigerant Data Safety Data: R-410A Toxicity Liquid spatters can cause freeze burns. It is impossible skin absorption could result dangerous. It can be slightly irritating. Liquid has a degrease effect. Defrost with water the affected zones. Take off carefully Contact with Skin contaminated clothing, since it could have been sticked on the skin in case of frostbite.
Page 53
WPHBA / WPHA COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS APPENDIX: SAFETY DATA R-410A Refrigerant Data Safety Data: R-410A Do not inhale concentrated vapours. Their concentration in the atmosphere should not exceed the minimum preset values and should be maintained below the General Precautions professional threshold.
Page 54
Subject to modifications without prior notice.