Huawei IDS1000 User Manual page 11

Container data center single-zone fire extinguishing system
Table of Contents

Advertisement

IDS1000 Container Data Center
User Manual
Item
Solenoid valve output loop
Output loop current limit for other drivers
Gas Extinguishing Equipment
The gas extinguishing equipment uses heptafluropropane as the extinguishing agent. It
consists of components such as the extinguishing agent vessel, gas supply pipe, pressure
annunciator, and solenoid valve driver.
Table 1-3
Table 1-3 Specifications for the heptafluropropane gas extinguishing equipment
Item
Dimensions
Maximum operating pressure
Storage pressure
Storage container volume
Heptafluropropane filling density
Startup current
Startup voltage
VESDA
A VESDA consists of the host, power box, and sampling pipe. The VESDA host includes two
types: VLS and VLP. The VLS is a four-pipe scanning detector that can monitor each pipe and
generate alarms. The VLP is a standard detector that can only conduct general monitoring but
not for each pipe. The host should be configured based on practical requirements.
The detector host consists of a suction pump, filter, high-sensitivity smoke detector, and
precision electrical analyzer. The fan sucks air samples from the monitored environment
through the air sampling pipe to the smoke detector, which will analyze and process the
samples and calculate the amount of smoke in the air. If the smoke density exceeds the preset
alarm threshold, the system blinks and sends alarm signals to the ECC.
A dedicated PPS-004 power box should be configured for the VESDA. The PPS-004 power
box should be supplied by a 220 V AC main input and supplies 24 V DC power to the
VESDA host. Backup batteries should be deployed for the PPS-004 power box.
The features of the VESDA are as follows:
Issue 01 (2014-3-15)
lists the specifications for the gas extinguishing equipment.
High sensitivity and wide sensitivity adjustment range (0.005–20% obs/m), able to detect
regular fires at an early stage as well as the particles generated by the softened insulation
layer of an overloaded power cable
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Configuration Description
Specifications
≤ 3 A
≤ 1 A
Specifications
Outer diameter of the steel vessel: 364 mm
50° C: 3.4 MPa
20° C: 4.2 MPa
70 L
≤ 1120 kg/m3
1.2 A
24 V DC
5