Operation; Parameter Settings; Operation Condition; Storage - Narada NPFC Series Operation Manual

Lithium iron phosphate battery (lifepo4 battery module for telecom)
Hide thumbs Also See for NPFC Series:
Table of Contents

Advertisement

Operation

Chapter
Three/03

Parameter settings

Lead-acid batteries can be replaced by lithium battery of NPFC series if power is matched. Table 3-1
is new parameter settings of power plant for lithium battery.
Table 3-1 Parameter Settings of Power Plant for NPFC Series Batteries
No.
Parameters
1
Float charge voltage
2
Equalization charge voltage
3
Standard charge current
4
Charge current limitation
5
Equalization charge interval
6
Equalization charge duration
7
Condition to equalization charge
8
Condition to float charge
9
Recovered LLVD voltage
10
LLVD
11
BLVD
12
Temperature compensation for float charge
13
Temperature compensation for equalization charge
Note:
1.Equalization charge is requested to switch off for NPFC series batteries.
2.Rectifier parameter shall be set according to specific site requirement based on battery units used.
3.If the battery connected more than 2 in parallel, the max. charge current recommend 0.5C.

Operation Condition

Table 3-2 Requirements for Operation Environment
Discharge
Temperature
Charge
Range (°C)

Storage

Discharge
Recommended
Charge
Temperature(°C)
Storage
Humidity
11
Units
Defaults
V
54.0
V
NA or 54.1
A
0.2C
A
0.5C ~ 1.0C
day
NA
H
NA
A
NA
A
0.05C
V
50.0
V
47.0
V
43.2
-mV/°C
NA
-mV/°C
NA
-20 ~ +60
0 ~ +60
0 ~ +40
+15 ~ + 35
+15 ~ + 35
+15 ~ + 30
5% ~ 95%
Storage and Installation
Chapter
Four/04
Storage
Storage temperature range:
0°C
to 40°C.
Storage battery should be at 50%-80%SOC.
Recharge charge before using to recover capacity loss of self-discharge during storage and
transport.
Recharge battery during long-term storage for self-discharge. Recharge program as follow table:
Storage temperature
Recharge interval
0°C-30°C
Every 6 months
30°C-40°C
Every 3 months
Storage battery over
40°C
or under
0°C
will reduce battery life,
Storage battery in dry and low temperature, well ventilated place
Battery performance degradation after long-term storage, please shorten shelf time as possible
as you can.

Installation

Unboxing & Inspection
Please study this manual before installation.
Please inspect the package before unboxing, if any destroy with appearance, contact with the
supplier as soon as possible.
This device shall be installed and operated by professionals.
Preparation for Installation
Batteries shall not be placed in direct sunshine or close to heat source.
Batteries shall be installed in place with good ventilation to assure enough heat dissipation.
Batteries shall be placed in are with clean ambient and low humidity.
Heavy weight shall not be placed on any cable.
Following are the tools possibly but not limited be use for installation:
Tool items (possibly but not limited)
NPFC Series
LiFePO
Battery Module for Telecom
4
Single Module Recharge Procedure
1) Charge with 0.2C to 100%SOC
2) Discharge with 0.2C to 0%SOC
3) Charge with 0.2C per module for 4 hours
12