Operation And Maintenance; Parameter Settings - Narada 6V Series Operation Manual

Valve regulated sealed lead acid battery
Table of Contents

Advertisement

Charge requirement
Charge requirement
More than two battery voltages in the battery
string are lower than 2.18V in floating operation
Recommend charging if float charge for
more than three months
Battery storage for more than 6 months
Before the battery is installed
and applied in the site.
After the battery discharged
Note:
(1) When the depth of discharge is large (usually more than 5~10% C
so that this charge mode is more adequate. When charges for 24 hours or the current drops below 0.005C
value is substantially constant for three consecutive hours, the charge is considered complete.
(2) The battery needs to be fully charged as soon as possible, the charge current can be increased appropriately, but it cannot
be higher than recommend value.
(3) If the battery is not recharged in time after discharge, or the power is off again during recharge, the insufficient-charged
batteries will be frequently discharge, thus the batteries will lose part of capacity in short period. And it may cause capacity
loss at initial stage and the batteries will be rejected if the situation is serious.
Battery recharge method
Step 1: Connect the batteries in series, and ensure that the bolts and screws are fastened.
Step 2: Connect the positive and negative poles of the battery to the positive and negative poles of the charging device.
Step 3: Turn on the charging power supply, set the charging current limit value and charging voltage value according to the
supplementary power requirements;
09
Charge mode
Note
Charge current:
Equalization charge
Limited current I
~2.5I
10
10
Equalization charge
Charge voltage:
Limited voltage 2.35V/cell
Complement charge
Complement charge
Charge time:
24 hours
), it is recommended to use the equalization voltage,
10
A, and the current
10

operation and Maintenance

Chapter
three/03
|

Parameter settings

Table 3-1 Switching power supply parameter setup table (48V system, 25°C)
Parameter name
Floating Voltage(V)
Acme, AcmeG, MP, MPG, GP, GPG,
12REXC, ICS, UDS, DT
HRL, HTB,HTB-F
Equalization Voltage(V)
Acme, AcmeG, MP, MPG, GP, GPG,
ICS, UDS, DT, HRL, HTB,HTB-F
12REXC
Charging Current(A)
Limited Current For Charge (A)
Equalization Charge Cycle(day)
Equalization Charge Time(h)
Condition to Change Float Charge To
Equalization Charge(mA/Ah)
Condition To Change Equalization
Charge To Float Charge(mA/Ah)
LLVD (V)
BLVD (V)
BLVD Recover Voltage(V)
High Voltage Warning(V)
Low Voltage Warning(V)
Temperature Compensate Ratio With
Floating Voltage(mV/°C per cell)
Temperature Compensate Ratio With
Equalization Voltage(mV/°C per cell)
High Temperature Warning(°C)
Acme, AcmeG, MP, MPG, GP, GPG,
12REXC, ICS, UDS, DT
HRL, HTB,HTB-F
6V&12V Serials
Tough power supply
Normal power supply
(Cyclic operation)
(Floating operation)
54.0
54.0
54.4
54.4
56.4
56.4
55.2
55.2
0.1C
0.2C
10
10
0.25C
0.25C
10
10
90
30
24
24
>50
>50
<5
<5
Please refer to table 3-2
49
50
57.6
57.6
46
47
-3
-3
-5
-5
35
35
45
45
10