④
After setting the floating charge voltage, move switch SW2 up to light the EQUAL lamp shown
below, to turn on equalizing charge mode.
Caution: Equalizing charge mode can be turned on by using the CHARGE switch on the
panel, but if the charge voltage goes below 3A it automatically returns to float
charge.
Use the voltmeter on the panel to check the charger's voltage as you turn the control RV3
⑤
inside the blank panel to set the equalizing charge voltage for the battery being used.
After finishing the settings, move switch SW2 down (floating charge mode), and then replace
⑥
the blank panel.
2.2.8.5 Prohibiting equalizing charge
Because equalizing charge is unnecessary for lead sealed batteries, set the floating charge voltage
and the equalizing charge voltage to 26.8 V, and then move switch SW5 up as indicated by the arrow
below, inside the blank panel to prohibit equalizing charge (CHARGE switch is disabled).
INSTALLATIONS
2-53