Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY
AND/OR PROPERTY DAMAGE.
The 36C03, 36C13 and 36D34 complete gas controls
combine into a single compact package the functions of
3-position gas cock, pressure regulator, 100% shut-off
automatic pilot, and main operator. Separate models
are available for use on 24 VAC, 120 VAC and .750 VDC
systems. These controls can be mounted in any orientation
except upside down.
MODELS AVAILABLE
Model No.
Voltage
36C03
24 volts
36C03A
120 volts
36C03U
.750 volts
36C13
24 volts
36C13A
120 volts
36C13U
.750 volts
36D34U
.750 volts
Pilot Gas Outlet:
Located at outlet end of the valve
Type of Gas
Suitable for all domestic heating gases
Pressure Rating: 1/2 lb. per sq. in.
Pressure Regulator Adjust Range (Typical, See
Control Label):
Natural Gas: 2.5 to 5.0" W.C.
LP Gas:
7.5 to 12" W.C.
Ambient Temperature: -40° to 175°F
Thermocouple:
(24V & 120V types): Use W-R Type HO6
(.750V Quick Drop Out Power Unit for
36D34 models only): Use W-R Type H19E
Pilot Generator (.750 volt types):
Use W-R Type G01A-32
Mounting: Any position except upside-down
Gas
Current
Nat.
.23 Amp
Nat.
.035 Amp
Nat.
DC
LP
.23 Amp
LP
.035 Amp
LP
DC
Nat./LP
DC
white-rodgers.com
36C03, 36C10, 36C13 and 36D34
Combination Gas Valves
(24 Volt, 120 Volt and .750 Volt Models)
INSTALLATION INSTRUCTIONS
ECO
Terminals
The 36C03 and 36C13 models are also available without
pressure regulator as a Model 36C10.
The 36D34 model is limited to .750 VDC applications and
is equipped with a "quick drop out" power unit for vented
gas hearth products.
PIPE SIZES/CAPACITIES
Capacity (BTU/hr) at
1" pressure drop across valve
Nat. Gas
Pipe Size
(1000 BTU/cu. ft.,
(inches)
64 Sp. Gr.)
1
3
⁄
" x
⁄
"
100,000
2
8
1
1
⁄
" x
⁄
"
230,000
2
2
1
⁄
" x
3
⁄
"
230,000
2
4
3
⁄
" x
3
⁄
"
280,000
4
4
Upright, 90° from upright or vertical
UPRIGHT
LEFT OR RIGHT
NOTE: Control shown may not be identical
to replacement control.
DESCRIPTION
SPECIFICATIONS
LP Gas
(2500 BTU/cu. ft.,
1.53 Sp. Gr.)
162,000
372,600
372,600
453,600
INLET BOSS
UP OR DOWN
ON
PART NO. 37-5781E
Replaces 37-5781D
1547