Samsung DVM S ECO AM XMDG Series Installation Manual page 53

Table of Contents

Advertisement

Optional item
Input unit
Oil collection
Main
interval
Temperature
to trigger
Main
defrost
operation
Fan speed
correction for
Main
outdoor unit
Silent mode
Main
for night-time
High-head
condition
Main
setting
Long-pipng
condition
setting
(Setting is
Main
unnecessary
if high-head
condition is set)
Energy saving
Main
setting
Not applicable
Main
Not applicable
Main
Channel
Main
address
Snow
accumulation
Main
prevention
control
Silent mode
for external
Main
contact
SEG1
SEG2 SEG3 SEG4
0
0
0
4
0
1
0
0
0
5
0
1
0
0
0
6
0
1
0
0
0
1
0
7
0
2
0
3
0
0
0
1
0
8
0
2
0
3
0
0
0
1
0
9
0
2
0
0
1
0
0
1
0
0
1
1
0
1
0
0
1
2
0
1
A
U
1
3
0 - 15
0
0
1
4
0
1
0
0
0
1
1
5
0
2
0
3
Function of the option
Factory default
Shorten the interval by 1/2
Factory default
Apply setting when the
product is being installed in
humid area such as near river
or lake
Factory default
Increase fan speed
Disabled (Factory default)
LEVEL 1
LEVEL 2
LEVEL 3
Disabled (Factory default)
Not applicable
Not applicable
Not applicable
Disabled (Factory Default)
LEVEL 1
Not applicable
Disabled (Factory default)
Enabled
Not applicable
Not applicable
Not applicable
Not applicable
Automatic setting
(factory default)
Manual setting for channel
0 – 15
Enabled
Disabled (Factory default)
-
LEVEL 1
LEVEL 2
LEVEL 3
Remarks
Increase the outdoor unit's
fan speed to maximum value
Enable silent mode for night-
time
When equivalent length of
farthest indoor unit from the
outdoor unit is over 100m
Energy saving mode triggers
when the room temperature
reaches desired temperature
while operating in heating
mode.
Address for classifying the
product from upper level
controller(DMS,S-NET 3,etc.)
During snow accmulation , the
fan may spin even when the
unit is not in operation
If the external contact interface
module (MIM-B14) is used,
entering the silent mode is
available with contact signal.