Installation Of Refrigerant Y-Joint - Samsung DVM S ECO AM XMDG Series Installation Manual

Table of Contents

Advertisement

Installation of Air-conditioner
AA

Installation of refrigerant Y-joint

Install the Y-joint horizontally or vertically.
❇ ❇
Install horizontally
Install vertically
❇ ❇
f
X
When using A-J type of Y-joint,connect the Y-joint to the pipe with the provided reducer.
f
X
When using K-Z type of Y-joint,connect the Y-joint to the pipe by cutting the inlet of the Y-joint or provided reducer
properly.
• Install the Y-joint within
• Make sure that the pipe does not break at Y-joint adn pipe connection.
Caution
• Keep a minimum straight line distance of 500mm or more before connecting Y-joint.
Reducer
Pipe
Front
Connect to outdoor unit
❇ ❇
Install the Y-joint within
horizontal or on the vertical.
30
±
°
15
on the horizontal or on the vertical.
Connect to other branch joint or
Rear
indoor unit
Pipe Connection
Reducer
Rear
±
°
15
on the
≥10~15mm
Main pipe
Minimum straight line distance
(500mm or more)