Samsung DVM S ECO AM XMDG Series Installation Manual page 52

Table of Contents

Advertisement

Setting outdoor unit option switch and key function
AA
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
Caution
While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
❇ ❇
❇ ❇
If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting mode.
-
If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored setting is
saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress, setting will be saved.
Optional item
Input unit
Emergency
operation for
Main
compressor
malfunction
Cooling
capacity
Main
correction
Capcity
correction for
Main
heating
Current
restriction
Main
rate
52
SEG1
SEG2
SEG3
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
2
0
0
0
0
0
0
0
0
0
0
0
0
3
0
0
0
0
1
1
SEG4
Function of the option
0
Disabled (Factory Default)
1
Not applicable
2
Not applicable
0
7-9 (Factory default)
1
5-7
2
9-11
3
10-12
4
11-13
5
12-14
6
13-15
0
3.0 (Factory default)
1
2.5
2
2.6
3
2.7
4
2.8
5
2.9
6
3.1
7
3.2
8
3.3
0
100% (Factory default)
1
95 %
2
90 %
3
85 %
4
80 %
5
75 %
6
70 %
7
65 %
8
60 %
9
55 %
0
50 %
1
No restriction
Remarks
Targeted evaporation
°
temperature [
C].
(When low temperature
value is set, discharged
air temperature of the
indoor unit will decrease)
Targeted high pressure
[MPa].
(When low pressure
value is set, discharged
air temperature of the
indoor unit will decrease)
When restriction option is
set, cooling and heating
performance may
decrease.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents