Configuring The Counter - Infinite AERINOS User Manual

Autonomous rtu
Table of Contents

Advertisement

4.2 Configuring the Counter

The command enables counting mode on DI 4. The Counter (0-65535) is cleared
according to a Clear Mode parameter, thereby acting as a Totalizer or a virtual
Analog Channel.
1150,n
1150:
Command ID
n:
1, CNT number
Scope: LP-MCU, COMM_MCU
4.2.1 Counter Scale factor
1154,n,f
1154:
Command ID
n:
1, CNT number
f:
0.000-0.999, Counter Scale factor
Scope: COMM_MCU
4.2.2 Set Counter Clear Mode
1158,n,m
1158:
Command ID
n:
1, CNT number
m:
0-2, 0 No Clear (Totalizer), 1 Clear on Sampling, 2: Clear on Logging.
Scope: LP-MCU
4.2.3 Set Counter High Alarm Limit
1155,n,ah
1155:
Command ID
n:
1, CNT number
ah:
0-65535, Alarm Limit
Scope: LP-MCU
4.2.4 Counter Alarm actions
The command establishes the actions on a Counter Alarm Event.
1156,n,hi
1156:
Command ID
n:
1, CNT number
hi:
Action selection
1 Send logged data after the Alarm Message
0 Plain Alarm Message without Data Transfer
Scope: COMM_MCU
4.2.5 Clear Counter Configuration
1160,n
1160:
Command ID
n:
1, CNT number
Scope: LP-MCU, COMM_MCU
BSC-50D User Guide
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bsc-50d

Table of Contents