5. Operation

5.1 Alarm Messaging

5.1.1 DI Alarm Event
Message contents
BSC-50 <CR>
ALARM MESSAGE <CR>
DI 1 <CR>
Earth Fault
5.1.2 Temperature Alarm Event
Message contents
BSC-50 <CR>
ALARM MESSAGE <CR>
Temperature <CR>
High Temp
36.2
5.1.3 CNT Alarm Event
Message contents
BSC-50 <CR>
ALARM MESSAGE <CR>
RAIN GAUGE <CR>
Rain Start
465
<CR>: Carriage return character (ASCII 13)

5.2 Status Messaging

The following is a typical Status message:
Message contents
BSC-50 <CR>
STATUS MESSAGE <CR>
ON <CR>
TOTAL: <CR>
SQ: ERR:x, MIN:y, MAX:y, AVG:y <CR>
BER: ERR:x, MIN:y, MAX:y, AVG:y <CR>
SMS Status Messages are sent only to users with Administrator Rights.
The Status Message can contain information concerning the GSM Signal Quality.
The information includes the following fields:
TOTAL: n, number of Samples
SQ: Signal Quality: ERR: x=number of invalid Samples, MIN, MAX, AVG: minimum,
maximum and average values, y=0-31 (Value Range)
BER: Bit Error Rate: ERR: x= number of invalid Samples, MIN, MAX, AVG: minimum,
maximum and average values, y=0-7 (Value Range)
BSC-50D User Guide
Item description
Unit Name
Fixed Header
Input Name
Message Text
Item description
Unit Name
Fixed Header
Input Name
Message Text
Actual AI value
Item description
Unit Name
Fixed Header
Input Name
Message Text
Actual Counter value
Item description
Unit Name
Fixed Header
Operation Status
Total Samples
Signal Quality
Bit Error Rate