Device Configuration; Configuring A Digital Input - Infinite AERINOS User Manual

Autonomous rtu
Table of Contents

Advertisement

4. Device Configuration

BSC-50D utilizes two processors: An ultra Low Power MCU (LP-MCU), operating
steadily and a Communication processor (COMM_MCU), operating on demand for
conserving power. Configuration commands concerning the Low Power MCU must be
followed by a special command in order to update the Low Power MCU configuration
(see 4.15).

4.1 Configuring a Digital Input

The basic command for DI configuration is:
1100,n,s,a,d
1100:
Command ID
n:
1-4, DI number
s:
Up to 15 characters, DI name (Text, may include space characters)
a:
0-3, Transition selection (0: No Alarm, 1: positive, 2: negative, 3: Both)
d:
0-255, Delay time in seconds
Scope: LP-MCU, COMM_MCU
4.1.1 DI Alarm actions
The command selects the actions for each DI Alarm transition.
1106,n,ng,ps
1106:
Command ID
n:
1-4, DI number
ng:
Selection for the negative transition
1 Send logged data after the Alarm Message
0 Plain Alarm Message without Data Transfer
ps:
Selection for the positive transition
1 Send logged Data after the Alarm Message
0 Plain Alarm Message without Data Transfer
Scope: COMM_MCU
4.1.2 Clear DI Configuration
1110,n
1110:
Command ID
n:
1-4, DI number
BSC-50D User Guide
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bsc-50d