DRP-3200 / DBR-3200 / DHP-1U
U s e r ' s M a n u a l

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DRP-3200 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Mean Well DRP-3200 Series

  • Page 1 DRP-3200 / DBR-3200 / DHP-1U U s e r ' s M a n u a l...
  • Page 2: Table Of Contents

    ......................Safety Guidelines ........................Introduction ......................Introduction ........................Features ......................Order Information ....................... Main Specification ............Mechanical Specification and Input/Output Terminals ................Unit Mechanism of Su ly Charger ................Mechanism of Whole Rack System .......................... Functions ..................... Input Voltage Range ....................
  • Page 3: Safety Guidelines

    DRP-3200,DBR-3200,DHP-1U User's Manual Safety Guidelines ◎ Risk of electrical shock and energy hazard, all failure should be examined by a qualified technician. Please do not remove the case from the supply/charger or rack shelf unit by yourself. ◎ Please do not change any component on the unit or make any kind of modification on it. ◎...
  • Page 4: Main Specification

    Figure 1-3: Safety label of DHP-1U ◎Whole system DHP-12K1UT-X DHB-12K1UT-X Use only DRP-3200 series of identical model. Use only DBR-3200 series of identical model. DRP-3200 series DBR-3200 series ,X=48, MODEL, Max. 4 DRP-3200 modules provide ,X=48, MODEL, Max.
  • Page 5 MODEL DBR-3200-24 DBR-3200-48 BOOST CHARGE VOLTAGE(Vboost)(default) 28.8V 57.6V FLOAT CHARGE VOLTAGE(Vfloat)(default) 27.6V 55.2V CONSTANT CURRENT(CC)(default) 110A By built-in potentiometer, SVR VOLTAGE ADJ. RANGE OUTPUT 23.5 ~ 30V 47.5 ~ 58.8V RECOMMENDED BATTERY 330 ~ 1000Ah CAPACITY(AMP HOURS) Note.3 LEAKAGE CURRENT FROM <1.5mA BATTERY (Typ.)
  • Page 6: Mechanical Specification And Input/Output Terminals

    MODEL DHP-12K1U DHP-12K1U DIMENSION Rack 400*482.6*44(L*W*H, with mounting bracket) ; 365*440*44(L*W*H, without mounting bracket) OTHERS 4.85Kg ; 3pcs/17.4Kg/1.8CUFT PACKING 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 ℃ of ambient temperature. NOTE 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
  • Page 7: Mechanism Of Whole Rack System

    2.2 Mechanism of Whole Rack System ADDRESS ADDRESS SWITCH SWITCH 4-M8 L=16 10 9 10 9 10 9 10 9 5-M4 L=4 5-M4 L=4 11.65 20.7 11.65 20.7 20.7 11.65 20.7 11.65 10 max. Air flow direction Module A Module D Module C Module B 10.2...
  • Page 8 ※ LED Status Indicators & Corresponding Signal at Function Pins For power supply system Description Green The power supply functions normally The LED will flash with red light when internal temperature reaches ℃ 60 ; under this condition, the unit still operates normally without entering Red Flashing OT .
  • Page 9: Functions

    ◎ For charger system RTH+ Temperature sense associated with the temperature compensation function. RTH- Not use. ◎ The Black wiring cable goes with the DBR-3200, used for battery temperature compensation. ※ Connector Pin No. Assignment( ) : RJ45 8 positions Pin No.
  • Page 10 3.5.2 Voltage adjustment of whole rack system by an external 0 -5 Vdc source (Output Voltage Programming) (1) Connect output of the external DC source to PV(PIN 26) and –V(PIN 24) on CN1, as shown in Figure3-1. (2) Relationship between the output voltage and the external DC source is shown in Figure3-2.
  • Page 11: Fan Speed Control

    Built-in fan-lock protection circuit, the output will shut off when the DC fans stop operating (fan-lock or broken wires). In the meantime, there will be a “HIGH” signal sent out through T-ALARM, referenced to GND AUX. Please remove the unit from your system and send back to our local distributor or MEAN WELL for repair. ◎...
  • Page 12: Hot-Swap Operation

    DHP-1U LOAD Twisted wires Figure Connection of Remote Sense DHP-1U Figure Connection of Local Sense 3.15 Hot Swap Operation ◎ Built-in "Oring MOSFET", the units can be installed/removed without tu ning power off. ◎ Insert units: Grasp the handle and push into the rack shelf through the rail. "Click"...
  • Page 13: Series Operation

    3.16.2 Operation of rack shelves in parallel ( DRP 32 - 00 system) ◎ Parallel operation is only suitable for the identical units (with the same model and the same output voltage/current). Up to rack shelves and the maximum supply units that can be connected in parallel is . 8 ◎...
  • Page 14: Auxiliary Power

    3.18 Auxiliary Output ◎ Built-in 5V/0.3A and 12V/0.8A auxiliary output. 3.19 DR 32 P- 00 PMBus Communication Interface ◎ DRP-3200 is compliant with PMBus Rev.1.1, the maximum communication speed is 100KHz and it has the capability of identifying up to16 addressed units.
  • Page 15 3.19.2 PMBus Command List ◎ The command list of the DR 32 P- 00 is shown in Table 3- . It is compliant with the standard protocol of PMBus Rev. 1.1. For more detailed information, please refer to PMBus official website http://pmbus.org/specs.html). Command Command Transaction...
  • Page 16: Dbr-3200 Pmbus Communication Interface

    3.19.3 PMBus Data Range and Tolerance ◎ Display parameters PMBus command Model Range Tolerance ±10V READ_VIN 80 ~ 264V ±0.36V 0 ~ 30V READ_VOUT ±0.48V 0 ~ 60V ±5.32A 0 ~ 160A READ_IOUT (Note. 1) ±2.68A 0 ~ 80A ± ℃ READ_TEMPERATURE_1 -40 ~ 100℃...
  • Page 17 3.20.1 PMBus Device Addresing and Charge Mode Selection Each DBR 3200 unit should have their unique and own device address to communicate over the PMbus 7 bit address setting pins are used to assign a device address for a DBR 3200 unit as shown in the below description A0-A2 allow users to designate the address for each DBR-3200 unit;...
  • Page 18 3.20.3 PMBUS, PV/PC or SVR Functions Users are able to fully control and design the entire charging behavior, without the charging curve, by one of the following means- PMBus command, PV/PC function or SVR adjustment, please refer to the previous chapter. The operating priority is, PMBus > PV/PC > SVR. NOTE: When operating in this mode, PMBus commands B0h/B1h…B8h can be set but there will be no response whereas other PMBus commands and functions work normally.
  • Page 19 Command Command Transaction # of data Description Code Name Type Bytes Constant current setting value of charging curve CURVE_CC R/W Word (format: Linear, N= -2) Constant voltage setting value of charging curve CURVE_CV R/W Word (format: Linear, N= -9) Constant voltage setting value of charging curve CURVE_FV R/W Word (format: Linear, N= -9)
  • Page 20 ◎ Definition of Command B8h CHG_STATUS: Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 High byte FVTOF CVTOF CCTOF BTNC NTCER EEPER Low byte FULLM Low byte Bit 0 FULLM:Fully Charged ode Status 0=NOT fully charged 1=fully charged Bit 1 CCM:Constant Current Mode Status 0=the charger NOT in constant current mode 1=the charger in constant current mode...
  • Page 21 3.20.5 PMBus Data Range and Tolerance ◎ Display parameters PMBus command Mode Range Tolerance ±10V READ_VIN 80 ~ 264V ±0.36V 0 ~ 30V READ_VOUT ±0.48V 0 ~ 60V ±5.32A 0 ~ 160A READ_IOUT (Note. 1) ±2.68A 0 ~ 80A ± ℃ READ_TEMPERATURE_1 -40 ~ 100℃...
  • Page 22: Notes On Operation

    Please refer to our specifications about PV/PC or SVR function. 3.21 CANBus Communication Interface ◎ For further CANBus information, Please contact MEAN WELL for detail. Notes on Operation Installation Method ◎ Mount the HP-1U in a 19 inch rack cabinet before operating.
  • Page 23: Derating

    De-rating ◎ When DR 32 P- 00/ DBR 32 - 00 units are operating at a lower AC input voltage, these units will de-rate their output current automatically to protect themselves, shown as Figure 4-2. 230VAC Input only (HORIZONTAL) ℃ AMBIENT TEMPERATURE ( ) INPUT VOLTAGE (VAC) 60Hz Figure 4-2...