General type din rail with three phase or high input range drh-120/drt-240/drt-480/drt-960 series

Advertisement

Quick Links

 Type:
General Type DIN rail with Three Phase or High Input Range
(Series:DRH‐120, DRT‐240, DRT‐480, DRT‐960)
DRH‐120‐24 
DRH‐120‐48 
DRT‐240‐24  
DRT‐240‐48  
DRT‐480‐24  
DRT‐480‐48  
DRT‐960‐24  
DRT‐960‐48  
 
 Introduction 
General  type  with  three  phase  or  high  input  range  is  a  DIN  rail  power  supply  series  with  a  high  input  range, 
340‐550Vac. Like other Mean Well's DIN series, they can be mounted on a TS35 Standard DIN rail. 
 
 Installation 
(1)Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 
in use to prevent it from overheating. Also a 10‐15 cm clearance must be kept when the adjacent device is a 
heat source. 
(2)The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on 
the  top  for  DRH‐120,  the  input  terminals  on  the  right  and  output  on  the  left  for  DRT‐240,  DRT‐480  and 
DRT‐960. Mounting orientations other than that, such as upside down, horizontal, or table‐top mounting, is 
not allowed. 
 
 
 
 
 
 
 
 
(3)Use copper wire only, and recommended wires are shown as below. 
AWG 
Rated Current of 
Equipment (Amp) 
Cross‐section of 
2
Lead(mm
 ) 
Note: Current each wire carries should be de‐rated to 80% of the current suggested   
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely  fixed  to  prevent  poor  contact.  If  the  power  supply  possesses  multi‐output  terminals,  please  make 
sure each contact is connected to wires to prevent too much current stress on a single contact. 
(4)Use wires that can withstand temperatures of at least 80°C such as UL1007. 
(5)Recommended wire strapping length is 5mm (0.197"). 
(6)Recommended screwdriver is 4mm, slotted type. 
(7)The recommended torque setting for terminals is 10 kgf‐cm (9 Lb‐in). 
Installation Manual
 
INPUT: 400 ‐500VAC 0.65A 50/60Hz 
INPUT: 400 ‐500VAC 0.65A 50/60Hz 
INPUT: 400 ‐500VAC 0.95A 50/60Hz 
INPUT: 400 ‐500VAC 0.95A 50/60Hz 
INPUT: 400 ‐500VAC 1.7A 50/60Hz 
INPUT: 400 ‐500VAC 1.7A 50/60Hz 
INPUT: 400 ‐500VAC 2.4A 50/60Hz 
INPUT: 400 ‐500VAC 2.4A 50/60Hz 
18 
16
6A 
6‐10A 
0.75 
1.00 
 
OUTPUT: 24V 5A 
OUTPUT: 48V 2.5A 
OUTPUT: 24V 10A 
OUTPUT: 48V 5A 
OUTPUT: 24V 20A 
OUTPUT: 48V 10A 
OUTPUT: 24V 40A 
OUTPUT: 24V 20A 
14
12
13‐16A 
16‐25A 
1.5 
2.5 
 
10 
25‐32A 

Advertisement

loading
Need help?

Need help?

Do you have a question about the DRH-120-24 and is the answer not in the manual?

Questions and answers

Summary of Contents for Mean Well DRH-120-24

  • Page 1 Installation Manual    Type: General Type DIN rail with Three Phase or High Input Range   (Series:DRH‐120, DRT‐240, DRT‐480, DRT‐960)   DRH‐120‐24  INPUT: 400 ‐500VAC 0.65A 50/60Hz  OUTPUT: 24V 5A  DRH‐120‐48  INPUT: 400 ‐500VAC 0.65A 50/60Hz  OUTPUT: 48V 2.5A  DRT‐240‐24   INPUT: 400 ‐500VAC 0.95A 50/60Hz  OUTPUT: 24V 10A  DRT‐240‐48   INPUT: 400 ‐500VAC 0.95A 50/60Hz  OUTPUT: 48V 5A  DRT‐480‐24   INPUT: 400 ‐500VAC 1.7A 50/60Hz  OUTPUT: 24V 20A  DRT‐480‐48   INPUT: 400 ‐500VAC 1.7A 50/60Hz  OUTPUT: 48V 10A  DRT‐960‐24   INPUT: 400 ‐500VAC 2.4A 50/60Hz  OUTPUT: 24V 40A  DRT‐960‐48   INPUT: 400 ‐500VAC 2.4A 50/60Hz  OUTPUT: 24V 20A     Introduction  General  type  with  three  phase  or  high  input  range  is  a  DIN  rail  power  supply  series  with  a  high  input  range,  340‐550Vac. Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail. ...
  • Page 2 Installation Manual   (8)Suggested  fuse  and  maximum  number  of  the  PSUs  that  can  be  connected  to  a  circuit  breaker  at  230V  are  shown as below.  Circuit breaker  Model  Fuse  C16  D16  DRH‐120  T4A/H250V  14  16  DRT‐240  F3A/L250V  8  10  DRT‐480  F6.3A/L250V  3  5  DRT‐960  F6.3A/L250V ...
  • Page 3 Installation Manual    Warning / Caution !!  (1)Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do  not remove the case of the power supply by yourself!  (2)Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides  together is not allowed.  (3)Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection!  (4)Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.    (5)Only install the unit in a pollution degree 2 environment (Note.1). (6)Please do not install the unit in places with high moisture or near the water.  (7)The maximum operating  temperature is 40°C for DRT‐240 and DRT‐480  series, 50°C for DRH‐120 series and  DRT‐960 series, please do not install the unit in places with high ambient temperature or near fire source.  (8)The FG (      ) must be connected to PE (Protective Earth).  (9)Output current and output wattage must not exceed the rated values on its specification.  (10)Disconnect system from supply voltage:  Before commencing any installation, maintenance or modification work: Disconnect your system from  supply voltage. Make sure that inadvertent connection in circuit will be impossible!  (11)For continued protection against risk of fire, replace only with same type and rating of fuse.  Pour ne pas compromettre la protection contre les risqué d’incendie, remplacer par un fusible de même  type et de memes caractéristiques nominales.    Note.1: Pollution Degree 2 applies where there is only non‐conductive pollution that might temporarily become  conductive due to occasional condensation. Generally refer to dry, well‐ventilated locations, such as  control cabinets.    Manufacturer:  MEAN WELL ENTERPRISES Co., Ltd.  No.28, Wuquan 3rd Road, Wugu District,    New Taipei City, Taiwan, 24891  Tel: +886‐2‐2299‐6100  Web: www.meanwell.com   ...

This manual is also suitable for:

Drh-120-48Drt-240-24Drt-240-48Drt-480-24Drt-960-24Drt-480-48 ... Show all