Instructions: Control Panel LCP 501
4. Mounting the LCP
Models MCD5-0021 to MCD5-0105: The LCP can be removed or
replaced while the starter is running. It is not necessary to remove
mains or control voltage.
Models MCD5-0131 to MCD5-1600: The bus bar and/or heatsink are
live whenever mains voltage is connected. Remove mains and
control voltage from the soft starter before removing the cover.
1. Use the template to drill four mounting holes and two holes for the
DB9 connector.
2. Apply the foam gasket to the back of the LCP.
3. Align the LCP over the holes and screw in place.
4. Plug the cable into the LCP and the soft starter.
MCD5-0021 to MCD5-0105
177HA615.10
MI.17.G1.02 - VLT is a registered Danfoss trademark
177HA616.10
MCD5-0131 to MCD5-1600