Heat Anticipator Settings; Perfect Humidity™ Control Connections - Bryant Preferred Series Installation Instructions Manual

Single package rooftop gas heating/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for Preferred Series:
Table of Contents

Advertisement

the terminal strip on the upper-left corner of the Controls Con-
nection Board. See Fig. 40.
NOTE: If thru-the-bottom connections accessory is used, refer to
the accessory installation instructions for information on routing
power and control wiring.
RACEWAY
HOLE IN END PANEL (HIDDEN)
Fig. 40 — Field Control Wiring Raceway

HEAT ANTICIPATOR SETTINGS

Set heat anticipator settings at 0.14 amp for the first stage and
0.14 amp for second-stage heating, when available.
PERFECT HUMIDITY™ CONTROL CONNECTIONS
Perfect Humidity Space RH Controller
NOTE: The Perfect Humidity system is a factory-installed option
which is only available for units equipped with belt-drive motors.
PROGRAMMABLE THERMOSTAT
Fig. 41 — Typical Rooftop Unit with Perfect Humidity Adaptive Dehumidification System and Programmable Thermostat
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT
RRS
SRTN
HUM
D1
D2
V+
Vg
Perfect Humidity system is not available for single phase (-J volt-
age code) models.
The Perfect Humidity dehumidification system requires a field-
supplied and field-installed space relative humidity control de-
vice. This device may be a separate humidistat control (contact
closes on rise in space RH above control setpoint) or a combi-
nation thermostat-humidistat control device with isolated con-
tact set for dehumidification control. The humidistat is normal-
ly used in applications where a temperature control is already
provided.
Connecting a Field-Supplied Humidistat
1.
Route the humidistat 2-conductor cable (field-supplied)
through the hole provided in the unit corner post.
2.
Feed wires through the raceway built into the corner post
(see Fig. 40) to the 24-v barrier located on the left side of
the control box. The raceway provides the UL-required
clearance between high-voltage and low-voltage wiring.
3.
Use wire nuts to connect humidistat cable to two PINK
leads in the low-voltage wiring as shown in Fig. 42.
Connecting a Field-Supplied Thermidistat device
1.
Route the Thermidistat multi-conductor thermostat cable
(field-supplied) through the hole provided in the unit cor-
ner post.
2.
Feed wires through the raceway built into the corner post
(see Fig. 40) to the 24-v barrier located on the left side of
the control box. The raceway provides the UL-required
clearance between high-voltage and low-voltage wiring.
3.
The Thermidistat has dry contacts at terminals D1 and D2
for dehumidification operation (see Fig. 41). The dry con-
tacts must be wired between CTB terminal R and the PINK
lead to the LTLO switch with field-supplied wire nuts.
Refer to the installation instructions included with the field-
supplied Thermidistat device for more information.
THERMOSTAT
Perfect Humidity™ FIOP
*Connection not required.
23
Unit CTB
X*
C
G
W2
W1
Y2
Y1
R