Application functions 400-427

setting of the feedback range and the Setup of the
Sleep mode function.
Additionally, this parameter group includes:
- Reset function.
- Flying start.
- Option of interference reduction method.
- Setup of any function upon loss of load,
e.g.because of a damaged V-belt.
- Setting of switching frequency.
- Selection of process units.
400 Reset function
(RESET FUNCTIO)
Value:
Manual reset (MANUAL RESET)
Automatic reset x 1 (AUTOMATIC X 1)
Automatic reset x 2 (AUTOMATIC X 2)
Automatic reset x 3 (AUTOMATIC X 3)
Automatic reset x 4 (AUTOMATIC X 4)
Automatic reset x 5 (AUTOMATIC X 5)
Automatic reset x 10 (AUTOMATIC X 10)
Automatic reset x 15 (AUTOMATIC X 15)
Automatic reset x 20 (AUTOMATIC X 20)
Infinite automatic reset (INFINITE AUTOMATIC)
Function:
This parameter allows a choice of whether to reset and
restart manually after a trip, or whether the frequency
converter is to be reset and restarted automatically. In
addition, there is a choice of the number of times the
unit is to attempt a restart. The time between each reset
attempt is set in parameter 401, Automatic restart time.
Description of choice:
If Manual reset [0] is selected, resetting must be
effected via the "Reset" key or via a digital input. If the
frequency converter is to carry out an automatic reset
and restart after a trip, select data value [1]-[9].
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.70.A1.02 - VLT is a registered Danfoss trademark
In this parameter group,
the special functions
the frequency converter
are set up, e.g. PID
regulation,
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
VLT® 7000 Booster
The motor may start without warning.