Relay outputs

Relay outputs 1 and 2 can be used to give the
present status or a warning.
Relay 1
1 - 3 break, 1 - 2 make
Max. 240 V AC, 2 Amp.
The relay is placed with
the mains and motor
terminals.
Relay outputs
Value:
No function (NO FUNCTION)
Ready signal (READY)
Standby (STAND BY)
Running (RUNNING)
Running at ref. value (RUNNING AT REFERENCE)
Running, no warning (RUNNING NO WARNING)
Local reference active (DRIVE IN LOCAL REF)
Remote references active (DRIVE IN REMOTE REF.)
Alarm (ALARM)
Alarm or warning (ALARM OR WARNING)
No alarm (NO ALARM)
Current limit (CURRENT LIMIT)
Safety interlock (SAFETY INTERLOCK)
Start command active (START SIGNAL APPLIED)
Reversing (RUNNING IN REVERSE)
Thermal warning (THERMAL WARNING)
Hand mode active (DRIVE IN HAND MODE)
Auto mode active (DRIVE IN AUTO MODE)
Sleep mode (SLEEP MODE)
Output frequency lower than f
Output frequency higher than f
Out of frequency range (FREQ RANGE WARN.)
Output current lower than
Output current higher than I
Out of current range (CURRENT RANGE WARN.)
Out of feedback range (FEEDBACK RANGE WARN.)
Out of reference range (REFERENCE RANGE WARN.)
Relay 123 (RELAY 123)
Mains imbalance (MAINS IMBALANCE)
Control word 11/12 (CONTROL WORD 11/12)
Aux Pump Control (CONTROL AUXILIARY PUMP)
Function:
Description of choice:
See description of [0] - [28] in Analogue/digital outputs.
Control word bit 11/12, relay 1 and relay 2 can
be activated via the serial communication. Bit 11
activates relay 1 and bit 12 activates relay 2.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.70.A1.02 - VLT is a registered Danfoss trademark
parameter 223 (F OUT < F LOW)
LOW
parameter 224 (F OUT > F HIGH)
HIGH
parameter 221 (I OUT < I LOW)
LOW
parameter 222 (I OUT > I HIGH)
HIGH
VLT® 7000 Booster
Relay 2
4 - 5 make
Max. 50 V AC, 1 A, 60 VA.
Max. 75 V DC, 1 A, 30 W.
The relay is placed on the control card,
see Electrical installation, control cables.
Relay no.
parameter
If the parameter 556 Bus time interval function
becomes active, relay 1 and relay 2 will become cut off
if they are activated via the serial communication.
1
2
323
326
[0]
[0]
[1]
[1]
[2]
[2]
[3]
[3]
[4]
[4]
[5]
[5]
[6]
[6]
[7]
[7]
[8]
[8]
[9]
[9]
[10]
[10]
[11]
[11]
[12]
[12]
[13]
[13]
[14]
[14]
[15]
[15]
[16]
[16]
[17]
[17]
[18]
[18]
[19]
[19]
[20]
[20]
[21]
[21]
[22]
[22]
[23]
[23]
[24]
[24]
[25]
[25]
[26]
[26]
[27]
[27]
[28]
[28]
[29]
[29]
[30]
[30]
75

Advertisement

Table of Contents
loading

Table of Contents