Bit 0: Host/Local (R/W)
0 = Local
1 = Host
Bit 1: Run/Stop (R/W)
0 = Stop
1 = Run
Bit 2: Load/Unload (R/W)
0 = Unload
1 = Load
Bits 3-4: Load Level (R/W)
00 = 25%
01 = 50%
10 = 75%
11 = 100%
Bit 5: Stopped in Auto Restart (R)
0 = Not Stopped in Auto Restart
1 = Stopped in Auto Restart
FIGURE 4-46 INTELLISYS RECIP SG CONTROLLER REGISTER 01-STATUS/CONTROL
Register 096: Language
0 = English
1 = Spanish
2 = Portuguese
Register 098: Recip Type
0 = ESV
1 = ESV Booster
2 = PHE, LLE, XLE 2 Stage
3 = PHE, DXE 3 Stage
4 = PHE 2 A/E Booster
5 = PHE 2 Stage Booster
Register 105: Starter Type
0 = Star-Delta
1 = Full Voltage
2 = Remote Star-Delta
3 = Remote Full Voltage
FIGURE 4-47 INTELLISYS RECIP SG CONTROLLER REGISTER CODES
Bit 0: Run/Stop (R)
0 = Stop
1 = Run
Bit 1: Constant Speed Mode (R)
0 = Not in Constant Speed Mode
1 = Constant Speed Mode
Bit 2: Auto Dual Mode (R)
0 = Not in Auto Dual Mode
1 = Auto Dual Mode
Bit 3: Load/Unload (R)
0 = Unload
1 = Load
FIGURE 4-48 INTELLISYS RECIP SG CONTROLLER STATUS ALARM HISTORY
Bit 6: Alarm (R)
0 = No Alarms
1 = Alarms
Bit 7: Warning (R)
0 = No Warnings
1 = Warnings
Bit 8: Constant Speed Mode (R)
0 = Not in Const. Speed Mode
1 = Constant Speed Mode
Bit 9: Auto/Dual Mode (R)
0 = Not in Auto/Dual Mode
1 = Auto/Dual Mode
Bits 10-12: Unused
Bits 13-15: Unit Type (R)
111 = Recip controller
Register 097: Units of Measure
0 = °F and PSI
1 = °C and PSI
2 = °C and Bar
3 = °C and kPa
4 = °C and kg/cm 2
Register 104: Regulation
0 = 2 Step
1 = 3 Step
2 = 5 Step 1
3 = 5 Step 2
4 = Inlet Regulation
Register 114: Mode of Operation
0 = Constant Speed
1 = Auto/Dual
Bit 4: Stopped Auto Restart (R)
0 = Not Stopped in Auto Restart
1 = Stopped in Auto Restart
Bits 5-6: Load Level
00 = 25% Load
01 = 50% Load
10 = 75% Load
11 = 100% Load
Bit 7: Unused
8