6.1.1 Setting start levels with controller
LC 220
Select the start levels via the DIP switches. Choose
between LOW and HIGH. The stop and alarm levels
are setup automatically according to the chosen start
level.
LOW
Start level
180
[mm]
Stop level
100
[mm]
Alarm level
350
[mm]
See the installation and operating instructions of the
controller for more information about the DIP
switches.
The preset values of start, stop and alarm levels can
be changed via the PC tool, which can be ordered as
accessory. Use product number 96705378.
LC 221
Go go [Setup], then [L_01] and choose between the
following start levels. The stop and alarm levels are
setup automatically according to the chosen start
level.
1
Start level
180
[mm]
Stop level
100
[mm]
Alarm level
350
[mm]
20
HIGH
500
100
600
2
3
4
5
250
350
450
500
100
100
100
100
400
550
600
600
6.1.2 Setting start levels with float switches
Set the start and stop level by adjusting the length of
the free cable (L).
Start
Stop
Fig. 23
Example start/stop levels for Unilift CC
We recommend start and stop levels corresponding
to a cable length between the minimum and
maximum indicated below.
Cable length (L)
Unilift KP
70 mm (min)
Start
Unilift KP
150
290
Unilift KP
250
Unilift KP
300
350
Cable length (L)
Unilift CC
100 mm (min)
Start
Unilift CC
5
350
Unilift CC
7
Unilift CC
350
9
Cable length (L)
Unilift
APB
100 mm (min)
Start
Unilift
430
AP35/50B
L
150 mm (max)
Stop
Start
Stop
140
335
100
150
345
110
200 mm (max)
Stop
Start
Stop
115
400
55
150
435
90
400 mm (max)
Stop
Start
Stop
320
460
140