Accurex XRUBS-140 Installation, Operation And Maintenance Manual

Steel grease fan

Advertisement

Quick Links

Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
General Safety Information
Only qualified personnel should install this fan.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity is present. If more information is needed,
contact a licensed professional engineer before moving
forward.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC) and the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electric Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be free
to rotate without striking or rubbing any stationary
objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than max cataloged fan
RPM. Adjustments to fan speed significantly affects
motor load. If the fan RPM is changed, the motor
current should be checked to make sure it is not
exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to a duct while the fan is
running.
Steel Grease Fan
These belt drive upblast centrifugal exhaust fans are specifically
designed for high grease applications.
The maximum continuous operating temperature is 400°F (204.4°C).
Fan is available in nine sizes, 140-200 HP with nominal wheel diameter
ranging from 14 to 20 inches (356 to 508 mm). Each fan shall bear
a permanently affixed manufacturer's embossed metal nameplate
containing the model number and individual serial number.
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power
source can result in fire, shock or serious injury.
When servicing the fan, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
Precaution should be taken in explosive atmospheres.
Pour écarter les risques d'incendie, de choc électrique
ou de blessure grave, veiller à toujours débrancher,
verrouiller et étiqueter la source de courant avant
l'installation ou l'entretien.
Lors de toute intervention sur la soufflante, le moteur
peut être suffisamment chaud pour provoquer une
douleur voire une blessure. Laisser le moteur refroidir
avant toute maintenance.
Faire preuve de précaution dans les atmosphères
explosives.
Document 470311
Model XRUBS
Steel Grease Fan
DANGER
CAUTION
CAUTION
DANGER
ATTENTION
ATTENTION
Steel Grease Fan
1

Advertisement

Table of Contents
loading

Summary of Contents for Accurex XRUBS-140

  • Page 1 Document 470311 Model XRUBS Steel Grease Fan Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
  • Page 2: Table Of Contents

    Table of Contents Hook with Safety Latch General Safety Information ..... . 1 (Supplied by others) Receiving, Unpacking, Handling, Storage, Inspection and Maintenance During Storage, (2) Bearing Plate Lifting Points...
  • Page 3: Inspection And Maintenance During Storage

    The unit should be stored at least 3½ inches (89 mm) Dimensional Data off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection. Outdoor Fans designed for outdoor applications may be stored outdoors, if absolutely necessary.
  • Page 4: Installation Typical Roof Mounting

    Installation Typical Roof Mounting Installation 12. A drain trough is provided on all fans for single- point drainage of water and residue. Some means IMPORTANT for collection of this residue must be provided, either a container directly under the trough or use Installation, troubleshooting and parts replacement of an adapter and pipe to carry the residue to a are to be performed only by qualified personnel.
  • Page 5: Commercial Kitchen

    Commercial Kitchen Installation Commercial kitchen installations must comply with –Important– NFPA 96. Check local and national codes for these ELECTRICAL – If fan motor is NOT thermally protected, remote overload protection must be installed having adequate rating as to Representation of installations and consult local code authorities for other voltage, frequency, horsepower, and full load current per phase.
  • Page 6: Pre-Starting Checks

    Pre-Starting Checks 1. Check all fasteners and setscrews for tightness. 9. If adjustments are made, it is very important to The wheel should rotate freely and be aligned as check the pulleys for proper alignment. Misaligned shown in Figure 8. pulleys lead to excessive belt wear, vibration, noise and power loss.
  • Page 7: Operation

    Operation Inspection 1. Before starting up or operating fan, check all Inspection of the fan should be conducted at the fasteners for tightness. In particular, check the first 30 minute and 24 hour intervals of satisfactory setscrews in wheel hub and pulleys. operation.
  • Page 8: Maintenance

    Maintenance Belt and Bearing Maintenance 1. Belts tend to stretch after a period of time. They DANGER should be checked periodically for wear and Disconnect and secure to the “off” position all tightness. When replacing belts, use the same type electrical power to the fan prior to inspection or as supplied with the unit.
  • Page 9: Recommended Bearing Lubrication

    Recommended Bearing Lubrication Fan Inlet Connections Frequency in Months In order to ensure proper fan performance, caution Note: If unusual environment conditions exist (extreme must be exercised in fan placement and connection to temperature, moisture or contaminants), more frequent the ventilation system. Obstructions, transitions, poorly lubrication is required.
  • Page 10: Troubleshooting

    Troubleshooting WARNING AVERTISSEMENT Before taking any corrective action, make certain unit Avant d’entreprendre toute action corrective, s’assurer is not capable of operation during repairs. que l’appareil ne pourra pas fonctionner durant les réparations. PROBLEM CAUSE CORRECTIVE ACTION Wheel rubbing inlet Adjust wheel and/or inlet cone.
  • Page 11: Parts List

    Parts List Each fan bears a manufacturer’s nameplate with model CAUTION number and serial number embossed. This information A fan manufactured with an explosion resistant motor will assist the local representative and the factory in does not certify the entire unit to be explosion proof. providing service and replacement parts.