Preparing The Site; Temperature Requirements; Humidity Requirements; Altitude Requirements - Cisco Nexus 92348GC-X NX-OS Hardware Installation Manual

Table of Contents

Advertisement

Preparing the Site

Temperature Requirements

The switch requires an operating temperature of 32 to 104 degrees Fahrenheit (0 to 40 degrees Celsius). If
the switch is not operating, the temperature must be between –40 to 158 degrees Fahrenheit (–40 to 70 degrees
Celsius).

Humidity Requirements

Buildings in which the climate is controlled by air-conditioning in the warmer months and by heat during the
colder months usually maintain an acceptable level of humidity for the switch equipment. However, if the
switch is located in an unusually humid location, use a dehumidifier to maintain the humidity within an
acceptable range.

Altitude Requirements

This switch is rated to operate at altitudes from 0 to 13,123 feet (0 to 4,000 meters) . If you operate this switch
at a higher altitude (low pressure), the efficiency of forced and convection cooling is reduced and can result
in electrical problems that are related to arcing and corona effects. This condition can also cause sealed
components with internal pressure, such as electrolytic capacitors, to fail or to perform at a reduced efficiency.
Temperature Requirements, on page 5
Humidity Requirements, on page 5
Altitude Requirements, on page 5
Dust and Particulate Requirements, on page 6
Minimizing Electromagnetic and Radio Frequency Interference, on page 6
Shock and Vibration Requirements, on page 7
Grounding Requirements, on page 7
Rack and Cabinet Requirements, on page 7
Cisco Nexus 92348GC-X NX-OS Mode Switch Hardware Installation Guide
2
C H A P T E R
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents