Pwm (Pwm Frequency); Acc (Auto Adaptation Of The Closed Loop Current Controller) - WEST PAM-195-P-PVG Technical Documentation Manual

Power amplifier for directional valves with ratiometric input
Table of Contents

Advertisement

5.5.4 PWM (PWM frequency)

Command
PWM
The frequency can be changed in the defined steps (61 Hz, 72 Hz, 85 Hz, 100 Hz, 120 Hz, 150 Hz, 200 Hz,
269 Hz, 372 Hz, 488 Hz, 624 Hz, 781 Hz, 976 Hz, 1201 Hz, 1420 Hz, 1562 Hz, 1736 Hz, 1953 Hz, 2232 Hz
and 2604 Hz). The optimum frequency depends on the valve.
Attention: The PPWM and IPWM parameters should be adapted when using low PWM frequencies
because of the longer dead times which forces a reduced stability of the closed loop control.

5.5.5 ACC (Auto adaptation of the closed loop current controller)

Command
ACC
Operation mode of the closed loop current control.
ON:
In automatic mode PPWM and IPWM are calculated depending on the preset PWM-frequency.
OFF:
Manual adjustment.
Page 23 of 27
Parameters
X
x= 61... 2604
Parameters
x
x= ON|OFF
PAM-195-P-PVG
Unit
Hz
Unit
Group
-
EXP
Group
STD
18.06.2019