To Turn Off Gas To Appliance; Checking & Adjustments - RBI Futera XLF Series Manual

Finned copper tube gas boilers and water heaters
Hide thumbs Also See for Futera XLF Series:
Table of Contents

Advertisement

5.
If the pressure signal is correct, measure the flue gas CO
should be between 9% and 9.5%.
a.
If CO
is correct, proceed to step 6.
2
b.
If CO
is not within this range, adjust the air trim adjust-
2
ment slightly (see Figure 19, page 26) on top of mixing box
to achieve a CO
of 9% - 9.5%.
2
c.
If adjusting the air trim adjustment does not correct the prob-
lem, contact technical support at the factory to troubleshoot
the problem.
6.
If CO
and pressure signal are correct, allow the boiler to reach
2
steady state and verify supply gas pressure and check input rates
as explained in the Gas Supply Piping section.
7.
Remove jumper on AA and allow boiler to settle into minimum
input. Observe the combustion readings to ensure the boiler is
operating correctly.
8.
When finished, disable the low fire hold switch and replace test
ports to normal state. Remove the manometer connections and
close the control panel door.
9.
The Futera XLF boiler allows for many modes of operation and
control methods. Reference the XLF HeatNet Control IOM.

to tUrn oFF GAs to AppLiAnce

1.
Set the operating control to its lowest setting.
2.
Turn off all electric power to the boiler if service is
to be performed.
3.
Close the manual main and pilot gas shut-off valves.
28
Finned copper tube gas boilers & water heaters – Boiler manual
. It
cHecKinG & ADJUstments
2
spark gap
With the main and pilot gas manual valves in the closed position
energize the unit. Look through the sight glass in the pilot tube to
observe the trial for ignition. Make sure that the spark is strong and
continuous. If not, check and adjust the spark gap as shown in Fig-
ure 20.
Figure 20
Proper polarity of the ignition transformer wiring is
import. Improper wiring of the ignition transformer
can result in an explosion causing extensive property
damage, severe personal injury or death!
Spark Gap
FTXLF-IOM-HN-1-110308 Copyright 2008 Mestek, Inc.