3.3 Special attention on 3-pole use (24 V or 42 V)

Using Slam® Trans -unit with 3-pole socket outlets (with bonding) is a simple way to solve the
problems with static electricity of relating equipment. By connecting the bonding cable
(supplied with transformer) to the local equipotential system at the site the secondary side
sockets do have correct potential. Relating equipment can have a three core cable (P, N,
Bonding) making it more simple and practical to do the connection of metal parts of relating
equipment (also external metal parts). No extra bonding arrangement required.

3.4 Connection to the supply

It is recommended that the unit is first connected to the mains before entering the explosion-
hazardous area.

3.4.1 Requirements for supply (electricity)

The following main requirements should be taken into account:
Supply voltage: Variation may be maximum +/- 6% from the value stated in the unit type
label.
Current: Maximum current of the system is 16 A.
Frequency: Standard 50 Hz if not otherwise stated in the type label.
Fuse protection: The supply has a fuse with a breaking capacity of at least 1500 A
Please observe the type label for further data.
3.4.2 Connecting relating equipment to the Slam® Trans
Slam® Trans -units are equipped with Ex –certified sockets in the factory. The type and
number of the sockets are considered as an option so they are added to the unit upon
customer's special request.
Please note that output current of 10A or output power of 200VA should not be exceed
and maximum ambient temperature is +50°C .