Daikin RXYSCQ-TV1 Series Technical Data Manual page 24

Hide thumbs Also See for RXYSCQ-TV1 Series:
Table of Contents

Advertisement

12
Installation
12 - 2 Refrigerant Pipe Selection
RXYSCQ-TV1
RXYSQ-TV1
RXYSQ-TY1
12
System pattern
Allowed connection ratio (CR)
Other combinations are not allowed.
·VRV DX· indoor units only
·RA DX· indoor units only
·VRV DX· indoor unit + ·AHU·
Mix
·AHU· only
Pair + multi
Notes
1. There is no restriction on the number of connectable ·BP· boxes.
2. ·EKEXV· kits are also considered indoor units.
3. Restrictions regarding the air handling unit capacity
4. Pair AHU = system with 1 air handling unit connected to one outdoor unit
Multi AHU = system with multiple air handling units connected to one outdoor unit
About ventilation applications
I. ·FXMQ_MF· units are considered air handling units, following air handling unit limitations.
- Maximum connection ratio when combined with ·VRV DX· indoor units: ·CR 30·%.
- Maximum connection ratio when only air handling units are connected: ·CR 100·%.
- Minimum connection ratio when only ·FXMQ_MF· units are connected: ·CR 50·%
For information on the operation range, refer to the documentation of the ·FXMQ_MF· unit.
II. ·Biddle· air curtains are considered air handling units, following air handling unit limitations:
For information on the operation range, refer to the documentation of the ·Biddle· unit.
III. ·EKEXV + EKEQ· units combined with an air handling unit are considered air handling units, following air handling unit limitations.
For information on the operation range, refer to the documentation of the ·EKEXV-EKEQ· unit.
IV. ·VKM· units are considered to be regular ·VRV DX· indoor units.
For information on the operation range, refer to the documentation of the ·VKM· unit.
V. Because there is no refrigerant connection with the outdoor unit (only communication F1/F2), ·VAM· units do not have connection limitations.
However, since there is communication via F1/F2, count them as regular indoor unit when calculating the maximum allowed number of connectable indoor units.
22
• Outdoor Unit • RXYSCQ-TV1
Total
Maximum allowed amount of connectable indoor units (·VRV,
RA, AHU·)
Capacity
Excluding ·BP· units and including ·EXV· kits.
50~130%
Maximum ·64·
80~130%
Maximum ·32·
50~110%
(3)
Maximum ·64·
(3)
90~110%
Maximum ·64·
(4)
• VRV Systems • RXYSCQ-TV1
Allowed capacity
VRV DX indoor unit
·RA DX· indoor unit
50~130%
-
(1)
-
80~130%
50~110%
-
(2)
(2)
-
-
Air handling unit (AHU)
-
-
0~110%
90~110%
3D097984

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxyscq5tv1Rxyscq4tv1

Table of Contents