Greenlee DM-200A Instruction Manual

Greenlee DM-200A Instruction Manual

Hide thumbs Also See for DM-200A:

Advertisement

INSTRUCTION MANUAL
MANUAL DE INSTRUCCIONES
MANUEL D'INSTRUCTIONS
DM-200A • DM-210A
DM-510A
Digital Multimeters
Multímetros digitales
Multimètres
numériques
Read and understand all of the instructions and safety information in this
manual before operating or servicing this tool.
Lea y entienda todas las instrucciones y la información sobre seguridad
que aparecen en este manual, antes de manejar estas herramientas o
darles mantenimiento.
Lire attentivement et bien comprendre toutes les instructions et les
informations sur la sécurité de ce manuel avant d'utiliser ou de procéder à
l'entretien de cet outil.
52047798 REV 1
© 2014 Greenlee Textron Inc.
3/14
1.800.561.8187
information@itm.com
www.
.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DM-200A and is the answer not in the manual?

Questions and answers

Summary of Contents for Greenlee DM-200A

  • Page 1 Lire attentivement et bien comprendre toutes les instructions et les informations sur la sécurité de ce manuel avant d’utiliser ou de procéder à l’entretien de cet outil. 52047798 REV 1 © 2014 Greenlee Textron Inc. 3/14 1.800.561.8187 information@itm.com www.
  • Page 2: Purpose Of This Manual

    The DM-510A is a true RMS meter. Safety Safety is essential in the use and maintenance of Greenlee tools and equipment. This instruction manual and any markings on the tool provide information for avoiding hazards and unsafe practices related to the use of this tool.
  • Page 3: Important Safety Information

    Electric shock hazard: Contact with live circuits could result in severe injury or death. All specifications are nominal and may change as design improvements occur. Greenlee Textron Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
  • Page 4 Important Safety Information Electric shock and fire hazard: • Do not expose this unit to rain or moisture. • Do not use the unit if it is wet or damaged. • Use test leads or accessories that are appropriate for the application. Refer to the category and voltage rating of the test lead or accessory.
  • Page 5 DM-200A • DM-210A • DM-510A Important Safety Information Electric shock hazard: • Unless measuring voltage, current, or frequency, shut off and lock out power. Make sure that all capacitors are discharged. Voltage must not be present. • Set the selector and connect the test leads so that they correspond to the intended measurement.
  • Page 6 Identification 1. Display 4-digit LCD (maximum reading is 5999) and bar graph. 2. Feature buttons Refer to explanations in the “Using the Features” section. 3. Selector Selects a function or turns power OFF. 4. ΩV Positive input terminal for all measurements except current. 5.
  • Page 7: Display Icons

    DM-200A • DM-210A • DM-510A Display Icons Bar graph element 27. M Mega (10 14. – Polarity indicator for bar graph 28. Ω 15. LoZ Low input impedance is active. 29. k Kilo (10 Low battery 30. Hz Hertz (frequency in cycles per second) 17.
  • Page 8: Using The Features

    Using the Features All Models • SELECT: Press momentarily to toggle between functions. • : Press and hold until backlight illuminates. Press and hold again to turn off. The backlight automatically turns off after approximately 30 seconds to extend battery life. •...
  • Page 9 DM-200A • DM-210A • DM-510A Using the Features (cont’d) • Disabling the Beeper: Hold down the RANGE button while turning the meter on to temporarily disable the beeper feature. Turn the selector to OFF and then back on to enable the beeper.
  • Page 10 1.11, and displays the result. This method is accurate if the input signal is a pure sine wave. The DM-200A and DM-210A are average-responding meters. The true RMS-reading method uses internal circuitry to read the true RMS value. This method is accu- rate, within the specified crest factor limitations, whether the input signal is a pure sine wave, square...
  • Page 11: Installing The Software

    DM-200A • DM-210A • DM-510A Using the Optional Software These meters are compatible with Greenlee DMSC-2U, an optically isolated computer interface cable and software. It allows measurements to be logged to a personal computer using the Microsoft ® Windows ®...
  • Page 12: Operation

    Operation Electric shock hazard: Contact with live circuits could result in severe injury or death. 1. Refer to the Settings Table. Set the selector to the proper setting, press SELECT (when instructed to do so), and connect the test leads to the meter. 2.
  • Page 13 DM-200A • DM-210A • DM-510A Operation (cont’d) Settings Table (cont’d) Set the These icons will Connect Connect To measure this selector to this appear on the the red the black characteristic … symbol … display … lead to … lead to …...
  • Page 14: Typical Measurements

    Typical Measurements Voltage Measurement Current Measurement 1.800.561.8187 information@itm.com www. .com...
  • Page 15 DM-200A • DM-210A • DM-510A Typical Measurements Resistance Measurement Continuity Check Capacitance Measurement Diode Measurement Reverse Bias Forward Bias 1.800.561.8187 information@itm.com www. .com...
  • Page 16 Typical Measurements Temperature Electric Field Detection (EF) Refer to “Using the Features” for complete instructions. A–Non-contact B–Contact 1.800.561.8187 information@itm.com www. .com...
  • Page 17 DM-200A • DM-210A • DM-510A Accuracy Refer to the “Specifications” section for operating conditions and temperature coefficient. Accuracy is specified as follows: ± (a percentage of the reading + a fixed amount) at 23 °C ± 5 °C (73.4 °F ± 9 °F), 0% to 75% relative humidity.
  • Page 18 Accuracy (cont’d) All Models (cont’d) AC Current Range (50 Hz to 400 Hz) Accuracy Burden Voltage (typical) 600.0 μA ± (1.0% + 0.3 μA) 0.1 mV/μA 6000 μA ± (1.0% + 3 μA) 60.00 mA ± (1.0% + 0.03 mA) 1.7 mV/mA 600.0 mA ±...
  • Page 19 DM-200A • DM-210A • DM-510A Accuracy (cont’d) All Models (cont’d) Accuracy of Frequency Ranges Display Range Accuracy 10.00 Hz to 65.53 Hz ± (0.03% + 0.03 Hz) 65.5 Hz to 655.3 Hz ± (0.03% + 0.3 Hz) 0.655 kHz to 6.553 kHz ±...
  • Page 20 Accuracy (cont’d) DM-210A and DM-510A Only Capacitance Temperature Range Accuracy Range Accuracy 60.00 nF ± (2.0% + 0.05 nF) -50 °C to 1000 °C ± (0.3% + 3 °C) 600.0 nF ± (2.0% + 0.5 nF) -58 °F to 1832 °F ±...
  • Page 21: Specifications

    DM-200A • DM-210A • DM-510A Specifications Display: LCD (6000) and 24-segment bar graph Polarity: Automatic Sampling Rate: Numeric Display: 5 per second Bar Graph Display: 40 per second Temperature Coefficient: Nominal 0.15 x (specified accuracy) per °C below 18 °C or above 28 °C Automatic Power Off: After 34 minutes of inactivity.
  • Page 22: Measurement Categories

    Statement of Conformity Greenlee Textron Inc. is certified in accordance with ISO 9001 (2000) for our Quality Management Systems. The instrument enclosed has been checked and/or calibrated using equipment that is traceable to the National Institute for Standards and Technology (NIST).
  • Page 23: Maintenance

    DM-200A • DM-210A • DM-510A Maintenance Electric shock hazard: Before opening the case, remove the test leads from the circuit and shut off the unit. Failure to observe these warnings could result in severe injury or death. Electric shock hazard: The fuses are an integral part of the overvoltage protection.
  • Page 24 DM-200A • DM-210A • DM-510A Lifetime Limited Warranty Greenlee Textron Inc. warrants to the original purchaser of these goods for use that these products will be free from defects in workmanship and material for their useful life, excepting normal wear and abuse.

This manual is also suitable for:

Dm-510aDm-210a

Table of Contents