Electrical Data - Daikin SkyAir Alpha Series Technical Data Manual

Table of Contents

Advertisement

3

Electrical data

3 - 1 Electrical Data
AZAS-MV1
AZAS-MY1
RZAG-MV1
RZAG-MY1
Symbols
RZASG-MV1
MCA: Minimum Circuit Ampere [A]
TOCA: Total overcurrent amps [A]
RZASG-MY1
MFA: Maximum Fuse Ampere [A]
MSC: Maximum current of the starting compressor [A]
RLA: Rated load amps [A]
OFM: Outdoor fan motor
IFM: Indoor fan motor
FLA: Full Load Ampere [A]
KW: Fan motor rated output [kW]
Notes
1. The RLA is based on the following conditions.
Cooling
Indoor temperature 27.0°C DB / 19.0°C WB
Outdoor temperature 35.0°C DB
Heating
Indoor temperature 20.0°C DB
Outdoor temperature 7.0°C DB / 6.0°C WB
2. TOCA is the total value of each overcurrent set.
3. Voltage range
The units are suitable for use with electrical systems in which the voltage supplied to the unit terminals is not below or above the listed range limits.
4. The maximum allowable voltage that is unbalanced between phases is 2%.
5. MCA is the maximum input current.
The capacity of the MFA must be greater than that of the MCA.
Select the MFA according to the table.
6. Select the wire size according to the MCA.
7. MFA is used to select the circuit breaker and the ground fault circuit interruptor.
Earth leakage circuit breaker
RZAG71-100MV1
Indoor
Outdoor
FCAHG71GVEB
RZAG71M7V1B
FCAG35AVEB
x2
RZAG71M7V1B
FCAG71AVEB
RZAG71M7V1B
FFA35A2VEB
x2
RZAG71M7V1B
FBA35A2VEB
x2
RZAG71M7V1B
FBA71A2VEB
RZAG71M7V1B
FNA35A2VEB
x2
RZAG71M7V1B
FUA71AVEB
RZAG71M7V1B
FAA71AUVEB
RZAG71M7V1B
FVA71AMVEB
RZAG71M7V1B
FDXM35F3V1B
x2
RZAG71M7V1B
FHA35AVEB
x2
RZAG71M7V1B
FHA71AVEB
RZAG71M7V1B
FCAHG100GVEB
RZAG100M7V1B
FCAG35AVEB
x3
RZAG100M7V1B
FCAG50AVEB
x2
RZAG100M7V1B
FCAG100AVEB
RZAG100M7V1B
FFA35A2VEB
x3
RZAG100M7V1B
FFA50A2VEB
x2
RZAG100M7V1B
FBA35A2VEB
x3
RZAG100M7V1B
FBA50A2VEB
x2
RZAG100M7V1B
FBA100A2VEB
RZAG100M7V1B
FNA35A2VEB
x3
RZAG100M7V1B
FNA50A2VEB
x2
RZAG100M7V1B
FUA100AVEB
RZAG100M7V1B
FAA100AUVEB
RZAG100M7V1B
FVA100AMVEB
RZAG100M7V1B
FDXM35F3V1B
x3
RZAG100M7V1B
FDXM50F3V1B
x2
RZAG100M7V1B
FHA35AVEB
x3
RZAG100M7V1B
FHA50AVEB
x2
RZAG100M7V1B
FHA100AVEB
RZAG100M7V1B
• Outdoor Unit • RZAG-MV1
Voltage
Power supply
MCA
range
17,5
17,6
17,4
17,8
18,2
17,6
50Hz ~
17,3
220-240V
17,9
17,4
17,6
17,6
18,2
17,8
27,4
26,9
26,6
26,7
27,2
26,8
27,9
27,2
27,0
50Hz ~
26,9
220-240V
27,0
27,4
26,4
27,2
26,9
27,0
27,9
27,2
27,4
• Split - Sky Air • RZAG-MV1
Compressor
TOCA
MFA
MSC
RLA
20
15,5
20
15,5
20
15,5
20
15,5
20
15,5
20
15,6
20
15,5
20
15,5
20
15,5
20
15,5
20
15,5
20
15,5
20
15,5
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
32
23,5
0.094+0.094
3D110014A
OFM
IFM
kW
FLA
kW
FLA
0,094
0,8
0,091
0,5
0,094
0,8
0.044 x2
0.3 x2
0,094
0,8
0,054
0,4
0,094
0,8
0.050 x2
0.4 x2
0,094
0,8
0.089 x2
0.6 x2
0,094
0,8
0,070
0,5
0,094
0,8
0.034 x2
0,3
0,094
0,8
0,046
0,9
0,094
0,8
0,048
0,4
0,094
0,8
0,117
0,6
0,094
0,8
0.034 x2
0.3 x2
0,094
0,8
0.060 x2
0.6 x2
0,094
0,8
0,091
0,8
0.75+0.75
0,221
1,3
0.75+0.75
0.044 x3
0.3 x3
0.75+0.75
0.039 x2
0.3 x2
0.75+0.75
0,117
0,7
0.75+0.75
0.050 x3
0.4 x3
0.75+0.75
0.050 x2
0.4 x2
0.75+0.75
0.089 x3
0.6 x3
0.75+0.75
0.089 x2
0.6 x2
0.75+0.75
0,127
1,0
0.75+0.75
0.034 x3
0.3 x3
0.75+0.75
0.060 x2
0.5 x2
0.75+0.75
0,106
1,3
0.75+0.75
0,064
0,4
0.75+0.75
0,238
1,2
0.75+0.75
0.034 x3
0.3 x3
0.75+0.75
0.060 x2
0.5 x2
0.75+0.75
0.060 x3
0.6 x3
0.75+0.75
0.060 x2
0.6 x2
0.75+0.75
0,150
1,3
3D110014A
3
3
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents