About the refrigerant ........... Daikin website (publicly accessible). 4.4.3 To determine the additional refrigerant amount ..10 ▪ The full set of latest technical data is available on the Daikin 4.4.4 To determine the complete recharge amount ..... 10 extranet (authentication required).
3 Preparation NOTICE Preparation Fix the outdoor unit to the foundation bolts using nuts with resin washers (a). If the coating on the fastening area is Preparing installation site stripped off, the nuts rust easily. WARNING The appliance shall be stored in a room without continuously operating ignition sources (example: open 4.1.2 To install the outdoor unit...
4 Installation ▪ Drill (a, 4×) and remove the knockout hole (b). 4× Ø6 mm ▪ Cut out the slits (c) with a metal saw. 4× Ø6 mm 2 Remove the burrs, and paint the edges and areas around the edges using repair paint to prevent rusting.
4 Installation NOTICE NOTICE Do not block the air vents. This could affect air circulation Make sure to use a recommended bubble test solution inside the unit. from your wholesaler. Do not use soap water, which may cause cracking of flare nuts (soap water may contain salt, which absorbs moisture that will freeze when the piping gets cold), and/or lead to corrosion of flared joints (soap water may contain ammonia which causes a corrosive...
4 Installation Charging additional refrigerant Before charging additional refrigerant, make sure the outdoor unit's external refrigerant piping is checked (leak test, vacuum drying). INFORMATION Depending on the units and/or the installation conditions, it might be necessary to connect electrical wiring before you can charge refrigerant.
4 Installation WARNING Then G1>40 m Use the table below to determine The refrigerant inside the unit is mildly flammable, but R1 (length=G1−40 m) and R2 normally does not leak. If the refrigerant leaks in the room (length=G2). and comes in contact with fire from a burner, a heater, or a cooker, this may result in fire, or the formation of a harmful G1≤40 m R1=0.0 kg.
4 Installation To determine the complete recharge amount (kg) (in case of 3 When 2–28 is reached, press the BS3 button once. size‑up liquid pipe size) 4 Change the setting to '1' by pressing the BS2 button once . Model Length (m) 5 Push the BS3 button once 3~15...
4 Installation NOTICE 4.5.1 About electrical compliance In Europe, the greenhouse gas emissions of the total RZAG71~140M7V1B refrigerant charge in the system (expressed as tonnes Equipment complying with EN/IEC 61000‑3‑12 (European/ -equivalent) is used to determine the maintenance International Technical Standard setting the limits for harmonic intervals.
4 Installation Routing through Choose one of the 3 possibilities: 1~50 Hz 3N~50 Hz the frame 220-240 V 380-415 V L1 L2 L3 L1 L2 L3 a Power supply cable b Interconnection cable Connecting to the When cables are routed from the unit, a frame protection sleeve for the conduits (PG insertions) can be inserted at the knockout...
5 Commissioning 4.6.2 To check the insulation resistance of the There are NO refrigerant leaks. compressor The correct pipe size is installed and the pipes are NOTICE properly insulated. The stop valves (gas and liquid) on the outdoor unit are If, after installation, refrigerant accumulates in the fully open.
6 Disposal Action Result Error code Possible cause Press. Test Operation is Nothing displayed ▪ The wiring is disconnected or there is a displayed on the home wiring error (between power supply and (the currently set menu. outdoor unit, between outdoor unit and temperature is not indoor units, between indoor unit and displayed)
7 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required). Overview: Technical data This chapter contains information about: •...