Eaton TA602LD Instruction Leaflet page 4

Amp circuit breakers, circuit breaker frame and molded case switch

Advertisement

Instruction Leaflet IL 29C703D
Effective April 2011
DWARNING
D
THEDVOLTAGESDINDENERGIZEDDEQUIPMENTDCANDCAUSEDDEATHDORDSEVERED
PERSONALDINJURY.DBEFOREDMOUNTINGDTHEDCIRCUITDBREAKERDINDAND
ELECTRICALDSYSTEM,DMAKEDSUREDTHEREDISDNODVOLTAGEDPRESENTD
WHEREDWORKDISDTODBEDPERFORMED.D
N
otee:
Depending on the equipment configuration, the circuit breaker can be
mounted using different styles of hardware . The following steps describe
how to mount the circuit breaker using standard hardware . When special
hardware is needed (for example, with the motor operator), the Instruction
Leaflet describing the accessory also describes the special mounting arrange-
ments .
2-6 . To mount the circuit breaker, perform the following steps:
a .
For individual surface mounting, drill the mounting panel using
the drilling plan shown in Figure 7 . For panelboard mount-
ing, only load end support mounting holes are required . For
Deadfront cover applications, cut out cover to correct escutch-
eon dimensions, see Figure 8 .
b .
If the circuit breaker includes factory or field installed internal
accessories, make sure accessory wire is accessible when
the circuit breaker is mounted .
N
otee:
Labels with accessory connection schematic diagrams are provided on
the side of the circuit breaker .
c .
Position the circuit breaker on the mounting surface .
d .
Install circuit breaker mounting screws and washers . Tighten
screws firmly, but do not exceed 28 lb .-in . (3 N .m) .
Line End
0.250-20
(M6-1.0)
Holes)
(4
5.052
(128.32)
9.531
(242.09)
4.479
(113.77)
1.375
(34.93)
Load End
Dimensions in Inches
(Millimeters)
Figure 7. 3-Pole Circuit Breaker Mounting Bolt Drilling Plans.
4
EATON CORPORATION www.eaton.com
Tap
Circuit
Breaker
Handle
2.750
(69.85)
Circuit
Breaker
Installation Instructions for Eaton Series C 600 Amp HLD-DC
Circuit Breakers, Circuit Breaker Frame and Molded Case Switch
,
3.438
(87.33)
1.719
(43.66)
I
Circuit
-
Breaker
-
Handle
0.250
(6.35)
I
Radius
0.188
(4.77)
Radius
3.641
(92.49)
7.281
(184.94)
Load End
Figure 8. Circuit Breaker Escutcheon Cutout Dimensions for
3-Pole Circuit Breakers.
DCAUTION
WHENDALUMINUMDCONDUCTORSDAREDUSED,DTHEDAPPLICATIONDOFD
ADSUITABLEDJOINTDCOMPOUNDDISDRECOMMENDEDDTODREDUCEDTHED
POSSIBILITYDOFDTERMINALDOVERHEATING.DOVERHEATINGDCANDCAUSED
NUISANCEDTRIPPINGDANDDDAMAGEDTODTHEDCIRCUITDBREAKER.D
2-7 .
Connect line and load conductors and accessory leads .
2-8 .
After the circuit breaker is installed, check all mounting hard-
ware and terminal connecting hardware for correct torque
loading . Torque values for line/load terminals are given in
Table 2 and on the circuit breaker nameplate .
2-9 .
Install both the line and load terminal covers on the circuit
breaker cover with mounting screws provided . Torque to
20-22 lb . in . (2 .26-2 .49 N .m) .
2-10 . When step-type terminals (Cat . No . TA603LD) are used, ter-
minal shields (supplied with terminals) must be installed on
the circuit breaker (Figure 9) and secured using retainer and
screws included with the terminal shield kit . Warning label
supplied with the kit must be attached to the circuit breaker
cover .
Line End
3-Pole
Circuit Breaker
3.281
(83.34)
1.325
(33.66)
2.292
(58.22)
1.500
(38.10)
D