Delta DPM-C520 Operation Manual page 53

Multi-functional power meter
Hide thumbs Also See for DPM-C520:
Table of Contents

Advertisement

D
5 2 0/ C5 2 0W O pe r at i on Ma n ua l
P M- C
1F
40032
20
40033
21
40034
22
40035
23
40036
_5
24
40037
34
40053
35
40054
36
40055
37
40056
38
40057
39
40058
3A
40059
3B
40060
5 - 4
5: Reset SSID, PWD, IP to
factory default
(available for DPM-C520W)
6: Reset wireless module
(available for DPM-C520W)
Alarm – Over Current
0: Disable
Alarm enable
1: Enable
Pickup setpoint
(current value
0.000 – 99999.999
exceeding this value
triggers alarm)
Dropout setpoint
(current value below
0.000 – 99999.999
this value clears
alarm)
Alarm – Over Voltage L–L
0: Disable
Alarm enable
1: Enable
Pickup setpoint (line
voltage value
0.000 – 99999.999
exceeding this value
triggers alarm)
Dropout setpoint (line
voltage value below
0.000 – 99999.999
this value clears
alarm)
Alarm – Under Voltage L–L
0: Disable
Alarm enable
1: Enable
word
float
A
Reserved
float
A
word
float
V
Reserved
float
V
Reserved
word
2
R/W
4
R/W
4
R/W
2
R/W
4
R/W
4
R/W
2
R/W

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dpm-c520w

Table of Contents