Gas condensing boilers. conversion to lpg p (g31)

Advertisement

B) CO
setting at the lower load (soft start)
2
• Restart the gas condensing boiler by pressing the
"Reset button".
• Check and if necessary correct the CO
30 s after the burner start with the CO
adjusting the zero point adjusting screw in accordance
with the table. Make this adjustment within 120 s of
the burner start. If necessary, repeat the start phase
for setting procedures by pressing the reset button.
• Turn clockwise - raises CO
• Turn anti-clockwise - lowers CO
Appliance open (without casing) at lower load
12.5% ± 0.2%
12
CO
settings
2
content approx.
2
tester, by fine
2
content.
2
content.
2
G31
Fig.: Gas combination valve.
Zero point screw, Tx40
Torx (under the cover)
Gas throughput screw
(slotted screw) only for
natural gas
3062883_0910