Parameters
Description
Manual mode limited to 5 minutes
UVS check (1 x in 24 hours)
Low fire over run time
Purge
Multi-flame control
Password
*
Adjustable using BCSoft software and a PC opto-adapter
** Please quote in your order.
0
= Function inactive
1
= Function active
On parameterisation, ensure that the program se-
quence started matches the application. Select the
parameters so that the burner can restart as intended
in all operating phases.

4 .1 Scanning the parameters

During operation, the 7-segment display shows the pro-
gram status.
The flame signal and all following parameters of the
PFU can be scanned one after the other by repeatedly
pressing the Reset/Information button (for 2 s).
In the event of a fault, the PFU halts the program run,
the display blinks and it then displays the cause of the
fault in coded form.
PFU 780 · Edition 02.12l
Parameter
Value range
34
0; 1
35
0; 1
36
0; 5; 15; 25 s
42
0; 1
45
0; 1
50
0000 – 9999
Factory default
Adjustable*
setting
1
0
0 s
1
0
1234
19