May 2019
A. 6234 ft. (1900 m) max (depending upon cable characteristics)
B. Integrated power conditioner and filter
C. Terminators
D. Trunk
E. Sput
F. Signal wiring
3.5.1
Ground the transmitter
Proper ground is crucial to reliable temperature readings.
3.5.2
Ungrounded thermocouple, mV, and RTD/Ohm inputs
Option 1
Procedure
1. Connect F
wiring shield(s).
2. Ensure the shields are tied together and electrically isolated from the
transmitter enclosure.
3. Only ground the shield at the power supply end.
4. Ensure that the sensor shield(s) is electrically isolated from the
surrounding grounded fixtures.
Quick Start Guide
B
™
Fieldbus signal wiring shield to the sensor
OUNDATION
Quick Start Guide
A
C
D
E
E
F
13