3.2
Using conduit entries
Figure 3-2: Conduit Entries
F
A. Sensor 1 and 2
B. Sensor 3 and 4
C. Sensor 5 and 6
D. Sensor 7 and 8
E. Power/signal
F. Cover screw
Procedure
1. Unscrew the four cover screws to remove the junction box cover.
2. Remove the five conduit plugs and install the user-supplied conduit
fittings.
3. Run pairs of sensor wires through each conduit fitting.
4. Install the sensor wires into the correct screw terminals.
5. Attach the F
6. Replace the enclosure cover and tighten all cover screws.
3.3
Sensor wiring and power supply
Compatible with eight independently configurable channels including
combinations of 2- and 3-wire RTDs, thermocouples, mV, ohm, and mA
sensors.
All sensor and power terminals are rated to 42.4 Vdc.
F
OUNDATION
32.0 Vdc and 22 mA maximum current draw.
For best network performance twisted, shielded pair cabling should be
used. Proper gage wire should be selected to maintain the 9.0 Vdc
minimum.