Download Print this page

LEGRAND 4 142 21 Quick Start Manual page 3

Isolating switch dx3 ? 63 a direct current, 800v

Advertisement

Isolating switch DX ≤ 63 A
direct current, 800V
5. GENERAL CHARACTERISTICS
Minimum operating voltage:
. 12 V DC per pole.
Shocks withstand rated voltage:
. Uimp = 8 kV.
Isolation voltage:
. Ui = 1000 V.
Isolation distance:
. The distance between contacts is more than 5,8mm when the
handle is in open position « O-Off »
. DX DC circuit breaker are suitable for the isolation in accordance
with EN/IEC 60947-3
Category of use:
. DC21B.
Rated short-time withstand current:
. Icw = 12 x In minimum.
Rated short-circuit making capacity:
. Icm = 1500 A.
Short-circuits withstand:
. Icc = 5000 A.
Effort to operate the handle:
. 0,5 Nm per device when closing the contacts.
. 0,3 Nm par device when opening the contacts.
Endurance:
. 20000 operations without load.
. 2000 operations at In and Un.
Enclosure material:
. Polyester.
. Characteristics of this material: self extinguishing, heat and fire
resistant according to EN 60898-1, glow-wire test at 960°C for
external parts made of insulating material necessary to retain in
position current-carrying parts and parts of protective circuit (650°C
for all other external parts made of insulating material).
Weight of the isolating switch:
. 0,581 kg.
Volume and packaging:
Double pole
Ambient temperatures:
. Operation: from - 25℃ to + 70℃
. Storage: from - 40℃ to + 70℃
Degree or class of protection:
. Protection index of terminals against solid and liquid bodies:
IP 20 (in according with standards IEC 529, EN 60529 and NF C
20-010).
. Protection index of the box against solid and liquid bodies:
IP 40 (in according with standards IEC 529, EN 60529 and NF C
20-010).
. Protection index against mechanical shocks: IK 02 (in according
with standards EN 50102 et NF C 20-015).
Technical data sheet : F01282EN/02
(continued)
Volume (dm
)
3
1,2 dm
3
Cat. n°(s) : 4 142 21 / 23 / 24 / 26
5. GENERAL CHARACTERISTICS
Sinusoidal vibration resistance in accordance with
IEC 60068.2.6:
. Axis : x, y, z.
. Frequency range: 5÷100 Hz ; duration 90 min.
. Displacement (5÷13,2 Hz) : 1mm
. Acceleration (13,2÷100 Hz) : 0,7g (g=9,81 m/s
Pollution degree :
. 3 in accordance with EN/IEC 60898-1.
Dielectric strength:
. 2000 V
Dissipated power (W):
. For the 2P isolating switch
In
16 A
2P
1,5
. Impedance of the isolating switch (Ω) = P dissipée
Derating of the isolating switch in terms of ambient
temperature :
. Reference temperature : 40 °C in accordance with EN/IEC 60947-3
standard.
. Rated characteristics of the isolator switch may be modified
depending on the ambient temperature inside the enclosure where it
is installed.
In (A)
- 25°C
16
21,9
25
34,5
32
45,8
63
88,1
In (A)
30°C
16
16,6
25
26,0
32
33,3
63
66,1
Updated : 24/08/2016
(continued)
).
2
25 A
32 A
63 A
2,4
3,1
5,5
In
2
Ambient temperature in °C
Current in Amps
- 10°C
0°C
10°C
20,0
18,7
18,0
31,5
29,5
28,3
41,0
37,8
36,5
80,6
75,6
72,5
Ambient temperature in °C
Current in Amps
40°C
50°C
60°C
16,0
15,4
14,7
25,0
24,0
22,7
32,0
30,7
20,1
63,0
59,8
56,1
created : 7/10/2011
20°C
17,3
27,2
34,9
69,9
70°C
14,1
21,7
27,8
52,9