Connecting CLIF-CBUSLC via RS485-1 to C-Bus

NOTE:
Always power each CLIF-CBUSLC and the connected C-Bus devices via separate transformers.
NOTE:
The max. C-Bus cable length is 1200 m (4000 ft).
NOTE:
If any devices are not electrically isolated, signal ground connection is recommended. See section "RS485 Standard"
on pg. 11.
NOTE:
If the CLIF-CBUSLC is connected at either of the line's two ends, an additional termination resistor (RT = 120 Ohm) is
necessary.
NOTE:
Regardless of the position of the CLIF-CBUSLC along the C-Bus, the 3-position switch must be set to MID.
Example: CLIF-CBUSLC and Connected C-Bus Devices