Exe junction box wiring (exe Incus only)
The terminal compartment on the Exe-Incus unit is sealed at the factory and should not be opened on
site. Instead, all wiring connections are made via the Exe junction box that is mounted adjacent to the
Incus unit.
Figure 3-15 Exe Incus Electrical Connection Drawing
Refer to
The Exe-Incus is configured for a standard 3-wire connection; cables should be connected in positions
+24 V, 0 V and current loop output connected to the mA terminal.
Cable entry is via suitable hazardous area approved and ingress protection certified cable glands
(customer supply) or conduit. Ensure cable glands are ingress protected to the same standard as the
enclosure to maintain certification and are suitable for the size of cable used. Cable glands and
conduit should be fitted in accordance with manufacturers' instructions.
Figure 3-15
for descriptions of the cable entries for the terminals inside the Exe Junction box.