Feeder Protection
REF610
Product version: C
13. Technical data
Table 3. Dimensions
Description
Width
Height
Depth
Weight
Table 4. Power supply
Description
Type
U
rated
aux
U
variation (temporary)
aux
Burden of auxiliary voltage supply under
quiescent (P
)/operating condition
q
Ripple in the DC auxiliary voltage
Interruption time in the auxiliary DC voltage
without resetting the protection relay
Time to trip from switching on the auxiliary
voltage
Internal over temperature limit
Fuse type
Table 5. Energizing inputs
Description
Rated frequency
Rated current, I
n
Thermal withstand capability
• Continuously
• For 1 s
• For 10 s
Dynamic current withstand
• Half-wave value
Input impedance
ABB
Value
Frame
Case
Frame
Case
Case
Protection relay
Spare unit
Value
REF610CxxHxxx
U
= 100/110/120/220/240 V AC
r
U
= 110/125/220/250 V DC
r
85...110% of U
(AC)
r
80...120% of U
(DC)
r
<9 W/13 W
Max. 12% of the DC value (at frequency ogf 100 Hz)
<50 ms at U
rated
aux
<350 ms
+100 ºC
T2A/250 V
Value
50/60 Hz ±5 Hz
0.2 A
0.5 A
20 A
5 A
50 A
<750 mΩ
177 mm
164 mm
177 mm (4U)
160 mm
149.3 mm
3.5 kg
1.8 kg
REF610CxxLxxx
U
= 24/48/60 V DC
r
80...120% of U
1 A
4 A
100 A
25 A
250 A
<100 mΩ
1MRS756295 G
(DC)
r
5 A
20 A
500 A
100 A
1250 A
<20 mΩ
9