ABB RELION 610 Series Product Manual page 13

Feeder protection
Table of Contents

Advertisement

Feeder Protection
REF610
Product version: C
Table 16. Electromagnetic compatibility tests
Description
EMC immunity test level meets the requirements listed below
1 MHz burst disturbance test, class III
• Common mode
• Differential mode
Electrostatic discharge test, class IV
• For contact discharge
• For air discharge
Radio frequency interference tests
• Conducted, common mode
• Radiated, amplitude-modulated
• Radiated, pulse-modulated
Fast transient disturbance tests
• Power outputs, energizing inputs, power
supply
• I/O ports
Surge immunity test
• Power outputs, energizing inputs, power
supply
• I/O ports
Power frequency (50 Hz) magnetic field
Power frequency immunity test:
REF610CxxHxxx and REF610CxxxxHx
• Common mode
• Differential mode
REF610CxxLxxx and REF610CxxxxLx
• Common mode
• Differential mode
Voltage dips and short interruptions
Electromagnetic emission tests
• Conducted, RF-emission (Mains terminal)
• Radiated RF-emission
CE compliance
ABB
Type test value
2.5 kV
1.0 kV
8 kV
15 kV
10 V (rms), f = 150 kHz...80 MHz
10 V/m (rms), f = 80...2700 MHz
10 V/m, f = 900 MHz
4 kV
2 kV
4 kV, line-to-earth
2 kV, line-to-line
2 kV, line-to earth
1 kV, line-to-line
300 A/m continuous
Class A
300 V rms
150 V rms
Class B
300 V rms
100 V rms
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
1MRS756295 G
Reference
IEC 60255-22-1, IEC 61000-4-18
IEC 61000-4-2, IEC 60255-22-2 and ANSI
C37.90.3-2001
IEC 61000-4-6 and IEC 60255-22-6
IEC 61000-4-3 and IEC 60255-22-3
ENV 50204 and IEC 60255-22-3
IEC 60255-22-4 and IEC 61000-4-4
IEC 61000-4-5 and IEC 60255-22-5
IEC 6100-4-8
IEC 60255-22-7 and IEC 61000-4-16
IEC 61000-4-11
EN 55011
EN 55011, class A, IEC 60255-25
EN 55011, class A, IEC 60255-25
Complies with the EMC directive 2009/108/EC
and LV directive 2006/95/IEC
13

Advertisement

Table of Contents
loading

This manual is also suitable for: