Section 7
SPA functions
7.2

Setting guidelines

The parameters for the Event (EVENT) function are set via the local HMI or PCM600.

EventMask (Ch_1 - 16)

7.2.1
The inputs can be set individually as:
NoEvents
OnSet , at pick-up of the signal
OnReset , at drop-out of the signal
OnChange , at both pick-up and drop-out of the signal
AutoDetect

LONChannelMask or SPAChannelMask

7.2.2
Definition of which part of the event function block that shall generate events:
Off
Channel 1-8
Channel 9-16
Channel 1-16

MinRepIntVal (1 - 16)

7.2.3
A time interval between cyclic events can be set individually for each input channel. This can be
set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no cyclic
communication.
7.3

Logical signal status report BINSTATREP

7.3.1

Identification

Function description
Logical signal status report
7.3.2

Functionality

The Logical signal status report (BINSTATREP) function makes it possible for a SPA master to
poll signals from various other functions.
28
It is important to set the time interval for cyclic events in an optimized way to
minimize the load on the station bus.
IEC 61850
identification
BINSTATREP
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-A72E490D-01F7-4874-B010-8BDE38391D88 v3
Communication protocol manual
1MRK 511 379-UEN A
IP14841-1 v1
M12811-3 v2
M12811-5 v2
M12811-15 v2
M12811-29 v3
M12811-34 v1

Advertisement

Table of Contents
loading

Table of Contents