Dip Switch Settings - York TIWM006B21S Installation And Maintenance Manual

Inverter-driven multi-split system heat pump air conditioners
Hide thumbs Also See for TIWM006B21S:
Table of Contents

Advertisement

8.6

DIP Switch Settings

(1) Turn OFF the power supply to both indoor and outdoor units before adjusting DIP switch settings.
Otherwise, the settings are invalidated and do not take effect.
(2) Correct DIP switch settings are shown here. Remove the panel to make these adjustments and
reattach when finished.
TIWM006B21S to TIWM012B21S
Switch Cover
PCB2
(3) Unit No. Setting
Setting is not required.
Indoor unit numbers are set by the auto-address function. If an indoor unit number setting is required,
set the unit number of all indoor units respectively and sequentially by following setting position. It is
recommended that you assign a number to each indoor unit from "1". A maximum of 64 indoor units
per refrigerant cycle can be connected to an H-LINK ll System. Though the available numbers range
from zero to 63, the applicable number for the 64
For the centralized control, this setting is required.
(4) Capacity Code Setting (DSW3)
No setting is required, due to setting before shipment. This switch is utilized for setting the capacity
code which corresponds to the capacity of the indoor unit.
Indoor Unit Capacity
(MBH)
Setting Position
(5) Refrigerant Cycle No. Setting (RSW2 & DSW5)
This setting is required. The unit arrives with all settings in the OFF position.
36
TIWM015B21S to TIWM030B21S
Unit No. Setting
DSW6 (Tens Digit)
RSW1 (Units Digit)
Setting
Position
ON
OFF
1 2 3 4 5 6
Before shipment, DSW6 and RSW1 are set at "0".
For the units supporting H-LINK II,
the unit No. can be set for Max. 64 indoor units
(No.0~63).
006
008
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
OFF
OFF
Refrigerant Cycle No. Setting
DSW5 (Tens Digit)
RSW2 (Units Digit)
Setting
Position
ON
OFF
1 2 3 4 5 6
Before shipment, DSW5 and RSW2 are set at "0".
For the units supporting H-LINK II,
the ref. cycle No. can be set for Max. 64 cycles.
(No. 0~63)
Switch Cover
PCB2
th
indoor unit in theory supplants the number "zero".
Ex.) Set at No.16 Unit
DSW6
Set by inserting
slotted screwdriver
into the groove.
0
1 2 3 4 5 6
Set No.1 Pin at ON side
RSW1
0
Set at "6"
012
015
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
OFF
OFF
Ex.) Set at No.5 Cycle
DSW5
Set by inserting
slotted screwdriver
into the groove.
0
1 2 3 4 5 6
Set All Pins OFF
RSW2
0
Set at "5"
DIP Switch PCB
(PCB2)
DSW5
RSW2
DSW6
RSW1
DSW9 DSW2
DSW3
SW1
ON
OFF
018
024
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
OFF
OFF
ON
OFF
030
ON
1 2 3 4 5 6
OFF
P5417052