Fail-Safe Function F_Min_Max; Introduction; Connections; Inputs - Siemens Simatic Manual

Fail-safe function blocks for storage and retrieval machines. distributed safety/tia safety advanced.
Hide thumbs Also See for Simatic:
Table of Contents

Advertisement

Fail-safe function blocks for storage and retrieval machines

3.10 Fail-safe function F_MIN_MAX

3.10.1

Introduction

A minimum/maximum value evaluation from up to 8 INTEGER values is implemented using the
F_MIN_MAX fail-safe function. In the context of the additional fail-safe function blocks from the
RBG_Failsafe_DS_V5_4 library, this block can be used, for example to select the most restrictive SLS
limit that is currently active.
3.10.2

Connections

3.10.2.1 Inputs

Name
Data type
IN1
Int
IN2
Int
IN3
Int
IN4
Int
IN5
Int
IN6
Int
IN7
Int
IN8
Int
MODE
Bool

3.10.2.2 Outputs

Name
Q
3.10.3

Principle of operation

3.10.3.1 Parameterization

1. The block is implemented as function. This means that when called, all inputs must be inter-
connected. If a minimum/maximum evaluation is to be performed using less than 8 signals,
then the signal sources should be interconnected a multiple number of times so that all of the
inputs are assigned at the block.
S7-Distributed Safety/SIMATIC Safety - fail-safe function blocks for storage and retrieval machines
Description
Operand 1 for evaluation
Operand 2 for evaluation
Operand 3 for evaluation
Operand 4 for evaluation
Operand 5 for evaluation
Operand 6 for evaluation
Operand 7 for evaluation
Operand 8 for evaluation
Selects minimum/maximum evaluation
0: minimum evaluation
1: maximum evaluation
Data type
Description
Depending on the mode MODE, minimum or maximum value
Int
of the 8 inputs
- 3-61 -