ABB Relion 650 Series Applications Manual page 172

Breaker protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Control
Operation of primary apparatuses
Select-Execute principle to give high security
Selection and reservation function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchrocheck
Pole discordance supervision
Operation counter
Suppression of mid position
The apparatus control function is realized by means of a number of function blocks
designated:
Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI
Bay control QCBAY
Position evaluation POS_EVAL
Bay reserve QCRSV
Reservation input RESIN
Local remote LOCREM
Local remote control LOCREMCTRL
The signal flow between the function blocks is shown in Figure 64. To realize the reservation
function, the function blocks Reservation input (RESIN) and Bay reserve (QCRSV) also are
included in the apparatus control function. The application description for all these functions
can be found below. The function SCILO in the Figure below is the logical node for interlocking.
Control operation can be performed from the local IED HMI. If the administrator has defined
users with the IED Users tool in PCM600, then the local/remote switch is under authority
control. If not, the default (factory) user is the SuperUser that can perform control operations
from the local IED HMI without LogOn. The default position of the local/remote switch is on
remote.