1MRK 505 355-UEN A
Section 3
3.1

Description of configuration REQ650

3.1.1

Introduction

The basic delivery includes one binary input module and one binary output module, which is
sufficient for the default configured IO to trip and close circuit breaker. All IEDs can be
reconfigured with the help of the ACT configuration tool in the PCM600 engineering platform.
The IED can be adapted to special applications and special logic can be developed, such as
logic for automatic opening of disconnectors and closing of ring bays, automatic load transfer
from one busbar to the other, and so on.
The basic IED configuration is provided with the signal matrix, mimic and the application
configuration prepared for the functions included in the product by default. All parameters
should be verified by the customer, since these are specific to the system, object or
application. Optional functions and optional IO ordered will not be configured at delivery. It
should be noted that the standard only includes one binary input and one binary output
module and only the key functions such as tripping are connected to the outputs in the signal
matrix tool. The required total IO must be calculated and specified at ordering.
The configurations are as far as found necessary provided with application comments to
explain why the signals have been connected in the special way. On request, ABB is available to
support the re-configuration work, either directly or to do the design checking.
3.1.1.1

Description of B11

A breaker bay connecting a transmission line to a busbar, with back-up protection functions
enabling single or three phase trip.
Application manual

Configuration

Section 3
Configuration
GUID-79B8BC84-4AAB-44E7-86CD-FF63098B009D v1
GUID-D9C6EAEB-A4EA-49BF-BE90-CC3CAF1CA476 v1