Gas Medium Supervision Ssimg; Identification; Application; Setting Guidelines - ABB Relion 650 Series Applications Manual

Breaker protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 355-UEN A
Table 26: General settings parameters for the Measurement function
Setting
Operation
PowAmpFact
PowAngComp
Mode
k
UGenZeroDb
IGenZeroDb
UBase (set in
Global base)
IBase (set in
Global base)
12.2

Gas medium supervision SSIMG

12.2.1

Identification

Function description
Gas medium supervision
12.2.2

Application

Gas medium supervision (SSIMG) is used for monitoring the circuit breaker condition. Proper
arc extinction by the compressed gas in the circuit breaker is very important. When the
pressure becomes too low compared to the required value, the circuit breaker operation shall
be blocked to minimize the risk of internal failure. Binary information based on the gas
pressure in the circuit breaker is used as an input signal to the function. The function
generates alarms based on the received information.
12.2.3

Setting guidelines

The parameters for the gas medium supervision SSIMG are set via the local HMI or PCM600.
Operation : Off/On
PresAlmLimit : Alarm setting pressure limit for gas medium supervision
PresLOLimit : Pressure lockout setting limit for gas medium supervision
TempAlarmLimit : Temperature alarm level setting of the gas medium
Application manual
Short description
Operation
Off / On
Amplitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & U
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, U and I
Zero point clamping in % of
Ubase
Zero point clamping in % of
Ibase
Base setting for voltage level
in kV
Base setting for current level
in A
IEC 61850
identification
SSIMG
Selected
Comment
value
On
Function must be
1.000
Typically no scaling is required
180.0
Typically no angle compensation is required.
However here the required direction of P & Q
measurement is towards busbar (Not per IED
internal default direction). Therefore angle
compensation have to be used in order to get
measurements in aliment with the required
direction.
L1L2
Only UL1L2 phase-to-phase voltage is
available
0.00
Typically no additional filtering is required
25
Set minimum voltage level to 25%
3
Set minimum current level to 3%
35.00
Set LV side rated phase-to-phase voltage
495
Set transformer LV winding rated current
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
63
Section 12
Monitoring
On
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v3
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v1
211

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion req650

Table of Contents